Nippon Vpro NS Скачать руководство пользователя страница 6

OSCNS209-EN 

6/7 

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CONTROL 

• Set to stabilize the MV value the PID constant of the 

adjustment meter.   

• The life of the actuator and the valve becomes short if 

the movement of MV value is used on unstable 
condition.   

• Use shielded wire for signal wiring where high level 

noise is generated or when the wiring distance is long. 

• When wiring, if wiring of a signal is mistaken, it will not 

operate correctly. Contact us when you use two valve 
or more by one controller or indicator.   

• Input signal circuit is non-isolated.   

Do not connect DC (-) wire to other DC (-) common.   

• The input signal and operation mode are set as 

follows. (Factory shipped)   

Input signal 

4 to 20 mA 

Operation mode Mode A 

Operation 

SHUT  by decreased signal 
OPEN by increased  signal 

OPERATION 

TESTING 

• Make sure that power supply voltage is correct. Also 

check operating position, wiring, speed and signals.   

• During trial operation, check that valve movement and 

output signal are correct.   

ATTENTION 

• Keep power supplied for built-in space heater to 

prevent condensation inside actuator.   

• Do not touch the moving parts of actuator in 

operation.   

• Never put anything on the actuator or make it into a 

foothold.   

ADJUSTABLE RANGE OF STROKE 

LAX-030

• SHUT by an input signal 4 mA and shipped. 
• It is not necessary to adjust the stroke.   

LAX-070 

• SHUT by an input signal 4 mA and shipped.   
• Can be adjusted in the range of 7 to 11.5 mm. 

(default stroke: 11.5 mm)   

MANUAL OPERATION 

PRECAUTIONS 

• Manual operation should be a temporary operation.   
• Be sure to turn off the power before manual operation. 

NOTE 

• See indicator during operation and check OPEN / 

CLOSE position to prevent overturn.   

• For manual operation, do not give more than the rated 

torque and make at a slow rate. Actuator might be 
damaged if excessive force is added.   

Manual operation is to put a wrench   
(width: 13 mm) 

turn manual shaft slowly. 

MAINTENANCE 

• To prevent electric shock, be sure to turn off the power 

when removing the actuator cover.   

• Perform the first time in the state of the first stage 

included in real operation.   

• Do the routine maintenance at least once in half a 

year.   

Inspection items 

• Confirm operation of opening and closing.   
• Confirm that an actuator is not hot excessively. 
• Confirm existence of abnormal noise and 

vibration during operation.   

• Confirm whether screws are loose or not.   
• Confirm that water or condensation no remains 

in the actuator.     

• Confirm that operate the hunting or move 

continuously at high frequency.   

OPEN

CLOSE

Содержание Vpro NS

Страница 1: ...pe Linear L A X N S 0 5 U U F 0 EQ L A X N S 0 5 U U F X E 1 5 NH type L A X N H 0 5 U U T 0 NP type L A X N P 0 1 K K T 0 1 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1 Actuator LAX 2 Valve NS NH NP 3 Voltage 1...

Страница 2: ...MPa 1 MPa Size mm 10 to 15 10 to 15 15 Material Body SCS14A SUS316 PEEK Trim SUS316 SUS316 HCr PLTD PEEK Seat F PTFE SUS316 None Stem seal Packing F PTFE PTFE PTFE Allowable Leak Rate Bubble tight Cl...

Страница 3: ...oint it at the time of the order Indication signal 0 mA SHUT 1 mA OPEN External load resistance less than 3 k Common in mode A B Resolution Less than 0 2 Duty cycle 100 200 V AC 100 110 220 V AC 50 30...

Страница 4: ...t us if you need to adjust trimmer Terminal board Mode A LAX 070 Adjustment of dead band Adjustment of dead band is useful to prevent hunting of the actuator Turning D B trimmer clockwise increases th...

Страница 5: ...ent distortion of the valve ENVIRONMENT Do not install in place where corrosive gas is present or where vibration is heavy 0 5 G or more When radiant heat causes the surface temperature of the control...

Страница 6: ...ver put anything on the actuator or make it into a foothold ADJUSTABLE RANGE OF STROKE LAX 030 SHUT by an input signal 4 mA and shipped It is not necessary to adjust the stroke LAX 070 SHUT by an inpu...

Страница 7: ...Replace the actuator Rainwater entered the actuator Added high harmonics noise from an inverter Attachment a filter for each inverter maker option Effect of high level noise Use the shielded wire and...

Отзывы: