INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

HANDLING & STORAGE 

HANDLING 

Proper care in handling the valve should be taken to 
prevent damage. Do not drop or throw it.   

STORAGE 

Store the valve in the protected area from dust, 
moisture, and direct sunlight. If possible, valve should 
be kept in the original packaging.   

CHECKING 

• Check the product code, power supply, and voltage 

before installation.   

• Make sure that the bolts are not loose.   

INSTALLATION 

PRECAUTIONS 

Flush the pipeline carefully before installing the valve. 
Foreign particles, such as sand or pieces of welding 
electrode, will damage the trim and seats.   

INSTALLATION NOTES 

• This type valve has a flow direction. Install the valve 

accordingly.   

• NS / NH / NP type has a flow direction. Install the 

valve accordingly.   

• When the Cv value is small, the foreign object 

contained in the fluid causes blockage. The filter is 
used in front of the valve.   

Threaded End Rc (NS / NH type) 

• If seal tape or sealant protrudes into the valve, 

malfunction may result.   
Pay attention to tape treatment and coating amount.   

Flanged-end (NP type) 

• Use only rubber gasket for plastic flange.   
• Use spring washer to prevent from decreasing 

surface pressure gasket when the temperature 
change happens frequently.   

• Tighten all bolts using crossover method to load the 

joint evenly.   

• Wafer type needle valve is put between two seats of 

flanged-end and tightened with long bolts.   

SUPPORT 

Use proper support to prevent distortion of the valve. 

ENVIRONMENT 

• Do not install in place where corrosive gas is present 

or where vibration is heavy (0.5 G or more).   

• When radiant heat causes the surface temperature of 

the control unit to exceed 50 °C, provide an 
appropriate shielding plate.   

• If there is a possibility that the fluid and drive part 

freeze, please take measures to prevent freezing.   

POSITIONING 

• Should be positioned through 90° upward from 

horizontal. Provide space around the product to allow 
manual operation, inspection and replacement work. 

• Maintenance space more than 90 mm upward from 

the actuator is required.   

OTHER NOTES 

Until the wiring is completed there must be no 
condensation or flooding in the interior of the actuator, 
after piping. Protective caps on the cable gland are 
not waterproof.   

WIRING 

• Do not wiring outdoors on a rainy day.   
• Check the power supply and voltage.   

Connect the signal as shown in the wiring diagram.   
Do not connect unnecessarily terminal.   

• Use suitable flexible cable ( 5 to 10.5 mm).   

Lock and seal the cable completely to prevent 
condensation inside the actuator.   

• Built-in terminal block can clamp up to 1.5 mm in 

diameter without using solderless terminal.   

• Allow proper cable slack for maintenance.   
• Actuator should be electrically grounded.   

Use the terminal marked ( ) inside the actuator.   

PREVENT DEW CONDENSATION 

• When installing the cover after wiring, perform the bolt 

by the temporary tightening procedure and the 
permanent tightening procedure to tightly and 
securely tighten the rubber packing so that water does 
not enter from the outside.   

• Tighten the cable gland nut so that there is no leakage 

from the wire entrance.   

Содержание Vpro NS

Страница 1: ...pe Linear L A X N S 0 5 U U F 0 EQ L A X N S 0 5 U U F X E 1 5 NH type L A X N H 0 5 U U T 0 NP type L A X N P 0 1 K K T 0 1 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1 Actuator LAX 2 Valve NS NH NP 3 Voltage 1...

Страница 2: ...MPa 1 MPa Size mm 10 to 15 10 to 15 15 Material Body SCS14A SUS316 PEEK Trim SUS316 SUS316 HCr PLTD PEEK Seat F PTFE SUS316 None Stem seal Packing F PTFE PTFE PTFE Allowable Leak Rate Bubble tight Cl...

Страница 3: ...oint it at the time of the order Indication signal 0 mA SHUT 1 mA OPEN External load resistance less than 3 k Common in mode A B Resolution Less than 0 2 Duty cycle 100 200 V AC 100 110 220 V AC 50 30...

Страница 4: ...t us if you need to adjust trimmer Terminal board Mode A LAX 070 Adjustment of dead band Adjustment of dead band is useful to prevent hunting of the actuator Turning D B trimmer clockwise increases th...

Страница 5: ...ent distortion of the valve ENVIRONMENT Do not install in place where corrosive gas is present or where vibration is heavy 0 5 G or more When radiant heat causes the surface temperature of the control...

Страница 6: ...ver put anything on the actuator or make it into a foothold ADJUSTABLE RANGE OF STROKE LAX 030 SHUT by an input signal 4 mA and shipped It is not necessary to adjust the stroke LAX 070 SHUT by an inpu...

Страница 7: ...Replace the actuator Rainwater entered the actuator Added high harmonics noise from an inverter Attachment a filter for each inverter maker option Effect of high level noise Use the shielded wire and...

Отзывы: