31
VPM/VPR 360
The heating element has two rows of pipes and a 3/4" RG connection.
Control valve (accessory): Select when ordering.
VPM/VPR 480-560
The heating element has two rows of pipes and a 3/4" RG connection.
Control valve (accessory): Select when ordering.
Flow/return
temperature
Air volume
m
3
/h
Supply air
temp.
°C
Output
kW
Pressure drop
(water)
kPa
Pressure drop
(air)
kPa
Water volume
l/h
70/40
1000
41.4
11.00
2.78
4.63
318
2000
34.8
17.30
6.43
14.40
501
3000
31.1
22.10
10.10
28.10
641
3600
29.6
24.50
12.20
37.80
712
60/30
1000
33.3
8.12
1.64
4.63
234
2000
28.2
12.70
3.71
14.40
365
3000
25.4
16.10
5.75
28.10
464
3600
24.2
17.80
6.93
37.80
514
50/30
1000
30.5
7.15
2.78
4.63
309
2000
26.2
11.30
6.39
14.40
487
3000
23.8
14.40
10.00
28.10
622
3600
22.7
16.00
12.10
37.80
690
Flow/return
temperature
Air volume
m
3
/h
Supply air
temp.
°C
Output
kW
Pressure drop
(water)
kPa
Pressure drop
(air)
kPa
Water volume
l/h
70/40
2000
36.9
18.70
2.58
9.41
543
3000
33.1
24.10
4.11
18.30
700
4800
29.0
31.80
6.78
39.50
921
5600
27.7
34.60
7.93
50.90
1002
60/30
2000
29.6
13.70
1.49
9.41
395
3000
26.7
17.50
2.34
18.30
505
4800
23.7
22.80
3.80
39.50
659
5600
22.7
24.80
4.42
50.90
716
50/30
2000
27.5
12.20
2.56
9.41
526
3000
25.0
15.70
4.06
18.30
678
4800
22.3
20.60
6.69
39.50
891
5600
21.5
22.40
7.82
50.90
969
Содержание VPR 120