Installation
Positioning the unit
Leave plenty of free space in front of the unit (see table).
When positioning the unit, you should always consider future service and maintenance. You have to be able to replace filters easily as
well as fans and other components. There has to be enough room for you to clean the unit easily. When cleaning the unit, water may
leak from the condensate drain. There must therefore be enough space to install a water trap in connection with the condensate drain.
X and Y = Recommended service distance. Z = Door swing radius.
Unit
X (mm)
Y (mm)
Z (mm)
VPR120
3150
810
525
VPR240
3450
910
575
VPR360
3645
1110
600
VPR480
3645
1235
600
VPR560
3645
1235
600
ATTENTION
It is important that the unit is installed in level to obtain a proper drain from the condensate tray.
ATTENTION
Even though the unit is quiet and has low vibrations, you should still take vibrations into account. To create separation
between the unit and the base, it is therefore recommended to install vibration dampers under the unit.To other build-
ing parts there should be approx. 10 mm distance.
X
Y
Z