Humidity
TIME
60 MIN
ENTER
4
HUMIDITY
LOW >1<
LOW
30%
HUMIDITY
HIGH >4<
HUMIDITY
LOW >”1”<
LOW
”30%”
HUMIDITY
HIGH >”4”<
ENTER
ENTER
ENTER
ENTER
ENTER
TIME
”60” MIN
ENTER
ENTER
ENTER
HUMIDITY
1
2
3
1. HUMIDITY LOW "1"
Option for selecting lower fan speed in case of low air humidity.
The value can be set to: OFF and 1, 2, 3.
2. LOW "30"%
Range adjustable between 15-45%. 30% is standard
3. HUMIDITY HIGH "4"
Option for selecting higher fan speed in case of high air humidity.
The value can be set to: OFF and 2, 3, 4.
4. TIME "60" MIN
Maximum duration of high fan speed due to high air humidity.
The time can be set from 1-180 min.
The
HUMIDITY
menu has a option for running at higher and/or lower fan speeds in case of high/low air
humidity.
Low fan speeds are only activated in winter operation and at air humidity levels below 30%.
High speeds are activated by a change from 10% to 5% compared to an average relative air humidity of
40% to 80% over the last 24 hours.
When the current air humidity decreases to the average relative air hu 3%, high speed
operation will end. If the time expires before the air humidity has reached this level, high speed
operation will end.
High fan speed is deactivated again when the air humidity falls to within 3% or less of the 24 hour
average.
When the time has expired, a new, elevated daily average is added, so the function is not immediately
re-activated.
Up to 3 minutes may elapse before the high/low fan speed has stabilised.
Flashing menu items are designated with
" "
.