CO
2
NORMAL
600ppm
3
2
FLOW
HIGH 3
HIGH
800ppm
FLOW
HIGH ”3”
HIGH
”800”ppm
ENTER
ENTER
ENTER
ENTER
NORMAL
”600”ppm
ENTER
ENTER
ENTER
CO
2
1
1. FLOW HIGH "3"
Option for selecting high fan speed in case of high CO
2
concentration. The
value can be set to: OFF and 2, 3, 4.
2. HIGH "800" ppm
Limit for maximum CO
2
concentration before operation at high fan speed
begins. (400-2500 ppm)
3. NORMAL "600" ppm
Limit for minimum CO
2
concentration before operation at normal fan speed
begins. (400-2500 ppm)
This menu is only available if CO
2
sensors have been mounted on the unit. CO
2
sensors are optional
equipment, NOT supplied together with the Comfort range.
The
CO
2
menu contains an option for selecting whether the unit will automatically run at the higher fan
speed in the case of high CO
2
levels.
Flashing menu items are designated with
" "
.
Combi 302 Polar Top (English)
BY NILAN