CutIn X .........lux value, measured by light sensor, at which the lighting in zone X is switched on
CutOut X ......lux value, measured by light sensor, at which the lighting in zone X is switched off
Df1 ..............daylight factor 1; relation between Lx ind1 and sensor
Df2 ..............daylight factor 2; relation between Lx ind2 and sensor
Df3 ..............daylight factor 3; relation between Lx ind3 and sensor
4.4. Terminal data (see ‘Quickguide’, D)
In this menu, you can view the status of a number of system components.
5. TECHNICAL DATA
RJ12 -1:
Pin1 supply ........................+
24V DC ±10% (SELV)
Pin2 supply ........................-
Pin3 I/O (170-40100) ........potentialfree contact
Pin4 Ch1 ............................NPN 24V / 25mA; short circuit proof.
Pin5 Ch2 ............................NPN 24V / 25mA; short circuit proof.
Pin6 Ch3 ............................NPN 24V / 25mA; short circuit proof.
RJ12 -2:
For updating software.
Not obligatory
.
Power consumption:
Active .................................6VA
Standby ..............................2VA
Ambient temperature ..........+5 to +50°C
Storage temperature ...........-20 to +60°C
Protection rating .................IP20
Dimensions .......................70mm(W) x 55mm(H)
CE in accordance with .........EN60669-2-1