66
05-711
Memory function:
Same as for Mode 2
With memory
- Briefly press input 1: the load is switched off.
- Press input 1 long: dimming down.
- Briefly press input 2: the load is switched on at previous level
- Press input 2 long: dimming up
- When dimming up: dimmer stops at max. value.
(Note: Do not press max. for more than 10s so the control does not
switch to 2-button operation without memory function).
- When dimming down: dimmer stops at min. value.
Without memory
Briefly press input 2: load is switched on at max. value
The other operations are identical to those ‘with memory’.
After a voltage interruption the analog control will be switched on again
at the previous value.
Operation of input 3 (connection terminals: COM terminal and
terminal 3):
Panic function (see 4.B)
B. Operation of the panic button
(see fig. 6)
A panic button can be connected to input 3 (connection terminals,
COM terminal and terminal 3). The panic button is a push button or
switch which activates the panic function when the contact is closed,
EN