Ref. 001
Tripping time (t). (If the results are not according with
the values in table 3, then the general warning sign will
appear).
⏐
DISPLAY
↓
The nominal leakage current of the displayed tripping
time.
Figure 5: An example of a test result of the tripping time
Table 3: Admissible ranges of disconnection times according to IEC 1008-1 standard
Type RCCB
I
2I
5I *
Remark
standard
0,3
0,15
0,04
max. tripping time (s)
selective
0,5
0,2
0,15
max. tripping time (s)
0,13
0,06
0,05
min. delay (s)
* For rated values I
Δ
N
≤
30mA the five-fold test current is 0.25A.
- Because of safety reason, the measuring of the contact voltage will be executed,
with half the nominal fault current, before any other parameter will be tested.
- A selective RCD has an integrated leakage current function because of the
required delayed trip out. That is why the operator must wait for 30 s before reaching
final. The influence of the test current for contact voltage measurement will be
compensated now.