CONNECTIONS
Powerdrive MD2SL Installation and maintenance
5077 - 2017.12 / b
en
Rating
Mains power supply
Motor
575V / 60Hz - 690 V / 50Hz
I
L
(A)
Fuses (1)
Cable cross-section
(mm²)
(3)
Ico (A)
Cable cross-section
(mm²)
(4)
Gg type
(1)
aR type (2)
Class J
( UL)
340TH
Heavy
260
315
500
350
3x120 + PE
270
3x150 + PE
Normal
330
400
550
450
3x185 + PE
340
3x185 + PE
400TH
Heavy
325
400
630
450
3x185 + PE
335
3x185 + PE
Normal
415
400
700
500
2x[3x120 + PE]
415
2x[3x120 + PE]
500TH
Heavy
415
400
700
500
2x[3x120 + PE]
390
2x[3x120 + PE]
Normal
470
500
800
600
2x[3x150 + PE]
500
2x[3x150 + PE]
600TH
Heavy
470
500
800
600
2x[3x150 + PE]
490
2x[3x150 + PE]
Normal
570
630
1000
--
2x[3x185 + PE]
580
2x[3x185 + PE]
750TH
Heavy
570
630
2x500
--
2x[3x185 + PE]
615
2x[3x185 + PE]
Normal
730
800
2x630
--
4x[3x120 + PE]
780
4x[3x120 + PE]
900TH
Heavy
730
800
2x630
--
4x[3x120 + PE]
720
4x[3x120 + PE]
Normal
885
1000
2x800
--
4x[3x150 + PE]
940
4x[3x150 + PE]
1200TH
Heavy
885
1000
3x500
--
4x[3x150 + PE]
900
4x[3x150 + PE]
Normal
1145
1250
3x550
--
4x[3x240 + PE]
1090
4x[3x240 + PE]
1500TH
Heavy
1145
1250
3x550
--
4x[3x240 + PE]
1075
4x[3x240 + PE]
Normal
1350
1600
3x630
--
1410
1800TH
Heavy
1350
1250
3x550
--
1355
Normal
1665
1600
3x630
--
1630
Note: The line current value
I
L
is a typical value which depends on the source impedance. The higher the impedance. the lower the
current.
(1) gG fuse or equivalent solution (fuses connected in parallel. preferably C type circuit-breaker. etc). This protection must always
be connected in series with aR semi-conductor fuses.
(2) Semiconductor aR fuses do not ensure the protection of the drive power supply line and must always be associated with a
protection device against overload. localized at the head of the line.
(3) The recommended mains cable cross-sections have been determined for single-core cable with a maximum length of 20 m. For
longer cables. take line voltage drop into consideration due to high cable length.
(4) The motor cable cross-sections are given for information only for a current corresponding to the value of the
Ico current at 3 kHz. a maximum length of 50 m. output frequency less than 100 Hz and an ambient temperature
of 40°C.
The recommended motor cables are shielded multicore type
.
The values supplied are typical values.
Example: Cable cross-section of 3 x (3 x 185 + 95) corresponds to 3 cables each consisting of 3 phase conductors
(cross-section 185 mm²) + earth conductors (cross-section 95 mm²).