MECHANICAL INSTALLATION
Powerdrive MD2SL Installation and maintenance
5077 - 2017.12 / b
en
2.3.3.5 - Recommendations and coolant circuit
connections
• Each cabinet cooling circuit is independent. and must be
connected independently to the coolant unit.
• Cabinet cooling circuits must not be connected in
series.
• To prevent clogging and loss of coolant effect. it is
advisable to install filters on the cooling unit.
• To make it easier to drain the cooling circuit. it is advisable
to use a by-pass valve in the main pipe and valves on each
cabinet inlet.
• The installation of a sensor for detecting the lack of
coolant flow is highly recommended