36
PARAMETER-SETTING INTERFACE AND OPTIONS
POWERDRIVE MD2CS Installation guide
4946 - 2017.12 / c
en
5.5 - Mains chokes
POWERDRIVE MD2CS
must be connected to an AC line
reactor.
Rating
Choke
Reference
Irated
(A)
Inductance
(µH)
Losses
(W)
60T & 75T
135 ST 0.26
135
0.26
150
100T & 120T
200 ST 0.26
200
0.26
220
150T
230 ST 0.19
230
0.19
280
180T
280 ST 0.13
280
0.13
320
220T & 270T
460 ST 0.078
460
0.078
500
340T & 400T
650 ST 0.055
650
0.055
750
470T
800 ST 0.045
800
0.045
850
570T
912 ST 0.035
912
0.035
950
270TH & 340TH
340 ST 0.21
340
0.21
700
400TH & 500TH
480 ST 0.14
480
0.14
800
A second line reactor can be added to reduce the harmonics
of the line current. In this case, two identical reactors are
connected in series.
E1
S1
E2
S2
E3
S3
L1
L2
L3
E1
S1
E2
S2
E3
S3
Mains supply
Required
choke
Optionnal
choke
Drive
• Weight and dimensions
L1
L
H
E1
E2
E3
S1
S2
S3
E1
E2
E3
S
E
D
D1
F
Choke
Dimensions (mm)
Fixings (mm)
Weight
H
L
D
L1
D1
F
kg
135 ST 0.26
237
290 201 250
146
Ø10
30
200 ST 0.26
266
299 237 200
150
Ø10
40
230 ST 0.19
269
304 239 200
158
Ø10
42
280 ST 0.13
290
300 218 225
142
Ø9
34
460 ST 0.078 340
340 220 240 129,5
Ø12,5
50
650 ST 0.055 436
356 258 240
175
2x Ø13
110
800 ST 0.045 468
350 279 250
167
2x Ø13
120
912 ST 0.035 410
420 299 325
228
2x Ø13
85
340 ST 0.21
500 480 335 300 225
Ø12
180
480 ST 0.14
420 440 340 250 200
Ø10
125
5.6 - Associated braking module and
resistors
Braking phases occur when energy is sent back from the
motor to the drive. Without an additional device, the maximum
power that POWERDRIVE MD2CS can absorb is limited to its
internal losses. If the application generates significant braking
power (inertia slowdown, braking, etc) a device should be
added to the standard product consisting in a braking module
(MD2TF400 or MD2THF330) and an external RF-MD resistor.
5.6.1 - Braking modules
MD2TF transistors consist of an IGBT transistor and a control
circuit.
Ratings
T
TH
Braking transistor
reference
MD TF 400
MD THF 330
Peak current (A)
400
330
Continuous current (A)
250
110
Minimum value of the
associated resistor (Ω)
1.8
3.5
• Dimensions
• Connexions
• Connect the braking resistor to the transistor MD2TF400
•
Connect a thermal relay Rth (not fitted), set to the stated
current for the resistor associated with it.
• Connect the P14 map to the associted connector on the
interface board of the drive (tilt the control board to access the
interface board).
• Connect DC+ et DC- to the drive DC bus bars with
connection clamps (ie Rittal ref. 3457.500).