23
COMMISSIONING
MDX-I/O M2M - Installation and commissioning manual
5340 en - 2017.07 / c
19.52
: Analog input 5 destination
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
This parameter should contain the number
of the parameter which you wish to assign to
analog input AI5.
Only numerical parameters can be assigned.
If an unsuitable parameter is programmed, no
assignment will be taken into account.
19.53
: AO2 Analog Output 1 source
Adjustment range :
00.00
to
21.51
Factory setting
:
00.00
Format
: 16-bit
This parameter is used to select the source
which you wish to assign to analog output
AO2.
19.54
: Analog Output AO2 scaling
Adjustment range : 0 to 4.000
Factory setting
: 1.000
Format
: 16-bit
Used to provide a numerical value in
proportion with the source parameter as an
output. However, in the majority of cases, this
setting is not necessary since the output is
automatically scaled, meaning that 100% as
an output corresponds to the maximum value
of the source parameter selected in
19.53
.
19.55
: Analog output AO2 level
Adjustment range : ±100.00%
Format
: 16-bit
Indicates as a percentage the analog output
level, before conversion into a 0-10 V or
4-20 mA signal according to
19.57
.
19.56
: Analog output 2 filter
Adjustment range : None (0), 4 ms (1), 8 ms (2),
16 ms (3), 32 ms (4).
Factory setting
: 8 ms (2)
Format
: 8-bit
None (0):
No filtering is applied to the AO2
analog output.
4 ms (1) to 32 ms (4):
Used to set the filter time constant applied to
analog output AO2.
19.57
: AO2 Analog Output mode
Adjustment range : +/-10V (0), 0-20 mA (1),
4-20 mA (2)
Factory setting
: 4-20 mA (2)Format: 8-bit
Used to choose the type of output signal.
+/- 10V (0):
+/-10V voltage output.
0 - 20 mA (1):
0 to 20 mA current output.
4 - 20 mA (2):
4 to 20 mA current output.