4.3.5.  Procedure for replacing a faulty AVR 

If  one  of  the  AVRs  is  faulty,  the  AVR  concerned  must  be  replaced.  This  change  can  be  made  (while 
observing the safety conditions), even while the installation is running, by performing the steps below: 
 

Step 1

: Isolating the AVR 

  Open the power disconnect terminals 

  Open the generator and mains voltage measurement disconnect terminals 

  Switch off the 24 VDC power supply which supplies the AVR control circuit 

 

Step 2

: Dismantling the AVR 

 

  Remove the AVR connectors  

  Disconnect the earth wiring 

 

Step 3: 

Physically removing the faulty AVR

 

 
 
Step 4

: Installing the spare AVR 

  Make sure that the AVR is firmly fixed on the plate 

 

Step 5

: Electrical connections 

  Wire up the earth connection 

  Wire up the connectors, in strict compliance with the plate wiring diagram 

 

CAUTION: Reversing the wiring can seriously damage the generator and the AVR. 

 
 

 

Step 6

: Supplying the AVR with power 

  Power up the 24 VDC power supply for the AVR control circuit 

  Check the AVR operation 

 

Step 7

: Loading the AVR configuration with the saved configuration (or if it is not available, using the 

configuration of the second AVR). 
 

Step 8

: Closing the disconnect terminals 

 

Step 9

: Checks 

  Set the AVR to "maintenance" mode  

  Check that the voltage and current measurements are in the same range. If this is not the case, please 

refer to section 3.4. Aligning measurements. 

  Reset "maintenance" mode on the AVR concerned 

  Check that the AVR reacts OK to the change of "maintenance" mode to "online" on the home page 

  Save the configuration of the AVR that has been replaced 

 
 
 
 
 
 
 
 
 
 

Содержание Leroy-Somer D700

Страница 1: ...Dual plate Installation and maintenance D700...

Страница 2: ......

Страница 3: ...of the cabinet housing the dual plate 10 2 2 Connection block 10 2 3 Consumption 13 2 4 Wiring precautions 13 3 Setup instructions 14 3 1 Stator voltage and current measurement 14 3 2 Configuration fi...

Страница 4: ...s for 10 seconds maximum 1 This plate has been designed to be installed in a control and power switching cabinet These cabinets must provide the minimum conditions for protection and safety of electri...

Страница 5: ...of the generator field circuit Two freewheel diode modules connected on the field circuit to ensure it never opens All the controls 9 configurable inputs hard wired to deliver the same information to...

Страница 6: ...ge 50 400 VDC 110 max 2 minutes Consumption 3000 VA Field current Rated 0 25 A Short circuit max 50 A at 25 C Field winding resistance 4 Ohm Frequency measurement Range 30 400 Hz For the plate 3 auxil...

Страница 7: ...Electric Power Generation Installation and maintenance 5747 en 2018 10 a Dual plate D700 7 Fixings 371 32 28 8 352 06 CG CG 750 750 119 5 725 725...

Страница 8: ...ally the prevention of direct or indirect contact when the plate is powered up LEROY SOMER declines all responsibility in the event of the above recommendations not being observed The various interven...

Страница 9: ...cation of the clearance between components during transportation and handling Avoid touching the electronic components and contact parts The dual plate D700 contains parts which are sensitive to elect...

Страница 10: ...you with any additional information you may require This manual is to be given to the end user 1 4 8 Protection of the equipment Auxiliary power supplies for the AVRs and the control circuit which ar...

Страница 11: ...1 XM 13 Phase NW2 L2 XM 15 Phase NW3 L3 XM 12 Phase NW1 L1 Mains voltage measurement AVR 2 XM 14 Phase NW2 L2 XM 16 Phase NW3 L3 XP 1 Power X1 Field power AVR 1 XP 3 Power X2 XP 5 Power Z1 XP 7 Power...

Страница 12: ...nd AVR 1 and 2 XC 16 Plate 24VDC XC 17 DI6 input command AVR 1 and 2 XC 18 Plate 24VDC XC 19 DI7 input command AVR 1 and 2 XC 20 Plate 24VDC XC 21 DI8 input command AVR 1 and 2 XC 22 Plate 24VDC XC 23...

Страница 13: ...cable length must never exceed 100 m To ensure compliance with standards IEC 61000 6 2 IEC 61000 6 4 and IEC 60255 26 shielded cables are essential in the case of a D700 installed outside the termina...

Страница 14: ...nd to the technical and electrical data of the generator on which the plate is to be installed It is therefore important to pay particular attention to the following settings Generator power rated vol...

Страница 15: ...is checked In both cases the drawing on the right is updated with the appearance of a second D700 On the Protections page the following faults are automatically activated Machine fault tab reactive p...

Страница 16: ...activated if the AVR is active DO2 and DO10 are activated if the AVR is online 3 3 Checks prior to commissioning First it is necessary to check the wiring and general operation of the plate Step 1 Ins...

Страница 17: ...t breakers are closed properly in the generator Check that the status of both AVRs is OFF 3 4 Aligning measurements Once these checks have been done make sure that the measurements on both AVRs give s...

Страница 18: ...ry or secondary values of the main stator current transformers and or isolating transformers General machine configuration Step 5 Setting the PF With the same load check the PF measurement on the wait...

Страница 19: ...the serial link The regulation context is then preserved in the event of switching and running in manual mode 4 3 4 Switching on a fault Several faults can cause switching from the active AVR to the o...

Страница 20: ...a circuit which monitors the power transistors If there is a discrepancy between the transistor command and its action the active AVR switches to fault mode and the online AVR switches to active mode...

Страница 21: ...ching does not occur that may then come from the sensing VT Note By default no action has been programmed for loss of sensing A significant bump may therefore occur on switching to the online AVR This...

Страница 22: ...that may then come from a fault in the link to the exciter Note By default no action has been programmed for reactive reverse power A significant bump may therefore occur on switching to the online AV...

Страница 23: ...is firmly fixed on the plate Step 5 Electrical connections Wire up the earth connection Wire up the connectors in strict compliance with the plate wiring diagram CAUTION Reversing the wiring can serio...

Страница 24: ...eck the functions work AVR internal power supply fault Replace the AVR Restart the plate with the procedure in section 4 3 5 Control 24 VDC power supply fault Plate general fault Replace the 24 VDC po...

Страница 25: ...is available under reference P5 198 0003 5 1 2 Wiring diagrams The wring diagram for the dual plate D700 is available under reference WD 198 0003 5 2 Preventive maintenance instructions Check that th...

Страница 26: ...Electric Power Generation Installation and maintenance 5747 en 2018 10 a Dual plate D700 26...

Страница 27: ...ient repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to operate in al...

Страница 28: ...www leroy somer com epg 2018 10 a Linkedin com company Leroy Somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel 5747 en...

Отзывы: