
Rev. 0 - 11/12/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
35/40
Holding Register 48:
Modbus Stop Bits [Adim] (Default = 0)
This register can be used to set the parity and the stop bits.
Allowed values
= table below
Default value
= 0
0
2 Stop Bits/No Parity
1
1 Stop Bit/Even Parity
2
1 Stop Bit/Odd Parity
Holding Register 50:
External Set [10
−1
V]
This register can be used to set the reference of the PID control.
Allowed values
= [0, 100]
Default value
= 0
The register is active when the Input Type Holding Register is set to the value 12.
Holding Register 51:
Kp [Adim]
This register can be used to set the Proportional Gain of the PID control.
Allowed values
= [0, 32767]
Default value
= 0
Holding Register 52:
Ki [Adim]
This register can be used to set the Integral Gain of the PID control.
Allowed values
= [0, 32767]
Default value
= 0
Holding Register 53:
Kd [Adim]
This register can be used to set the Derivative Gain of the PID control.
Allowed values
= [0, 32767]
Default value
= 0
Holding Register 54:
Period [ms]
This register can be used to set the time constant of the PID control.
Allowed values
= [0, 32767]
Default value
= 0
Holding Register 55:
Speed Threshold (or Speed Threshold HIGH) [RPM]
This register can be used to set the speed threshold, when the measured speed in the Input Register 3 overtakes the threshold value.
Allowed values
= [0, Max Speed]
Default value
= 0
Allowed values (Functioning Indication mode)
= [Speed Threshold Low, Max Speed]
Speed Threshold =0 means that it is
DEACTIVATED
Содержание EC FAN FDP
Страница 2: ......