34/40
Holding Register 36:
Maximum Power [W]
This register can be set to reduce the power out to the motor.
Allowed values
= [10, Default Value]
Default value
= table below
Value
1.05kW
1-Phase
1050
Holding Register 39:
Constant Airflow [m3/h]
*
This register can be used to set the constant airflow value.
The register is active when the Input Type Holding Register is set to the value 6.
*
This setting is not currently available. If necessary, contact Regal Beloit Italy S.p.A.
Allowed values
= [Min Airflow, Max Airflow]
Default value
= 0
Holding Register 45:
Modbus Address [Adim]
This register can be used to change the Modbus address of a driver.
Allowed values
= [1, 247]
Default value
= 1
Holding Register 46:
Tachometric / Alarm / Threshold [Adim]
This register can be used to set the digital output function.
Allowed values
= table below
Default value
= 0
The possible settings are:
0
Tachometric
The digital output indicates the measured speed through a PWM signal
1
Alarm
The digital output indicates when an alarm occurs
2
Threshold
The digital output indicates when the speed set in the Holding Register 55 is overtaken
3
Out of Functioning Range
The digital output indicates when the fan is working in a defined range of speeds
Holding Register 47:
Modbus Speed [10
−1
kbps]
This register can be used to set the Modbus speed.
Allowed values
= table below
Default value
= 96
96
corresponding to 9.6kbps
192
corresponding to 19.2kbps
384
corresponding to 38.4kbps (not available using the opto-insulated terminal block)
576
corresponding to 57.6kbps (not available using the opto-insulated terminal block)