
Rev. 0 - 11/12/2020
OPERATING MANUAL
OPERATING MANUAL
EN
EN
29/40
15. MASTER & SLAVE MODE
This single-phase driver has a tachometric output ranging from 0 to 5V and a special configuration must be set on the slave fan
for a Master&Slave connection. It is possible to drive two fans in a master and slave configuration by setting the MASTER in any
preferred mode and the SLAVE in Master&Slave mode only.
The SLAVE operating mode must be changed (
INPUT TYPE = 3
).
The MASTER must have the
Holding Register 46
set at 0 = TACHO.
15.1 Master and Slave 0-5V PWM out (for 1.05 kW 1-phase only)
A Master & Slave connection is necessary when the fans have to operate in parallel and in any Constant-Airflow mode, or under
control of the internal PID regulator. Having two or more fans self-controlling independently, while operating in parallel, can make
the system unstable. A Master & Slave connection is neither needed nor recommended when the fans in parallel are runnig in any
speed-control mode, even if under control of a common external PID regulator.
TACHO /
A
LARM / FIL
TER
TACHO /
A
LARM / FIL
TER
GN
D
GN
D
MODBUS -B
MODBUS -B
MODBUS -A
MODBUS -A
GN
D
GN
D
TRANSUCER INPU
T
TRANSUCER INPU
T
ANALOG INPU
T
ANALOG INPU
T
ENABL
E
ENABL
E
+10V
+10V
+24V
+24V
GND
GND
IN
IN
+10
+10
GND
GND
B
B
A
A
OUT
OUT
MASTER
SLAVE
MASTER
SLAVE
16 COMMUNICATION
Protocol interface:
MODBUS RTU (RS485 or Bluetooth)
Baud rate
The baud rate can be set through the
Holding Register 47
and the possible speeds are:
RS-485 CABLE
: 9.6kbps and 19.2kbps (higher speeds are not allowed due to the board Opto-Insulators)
UART OFFLINE CABLE
: 9.6kbps, 19.2kbps, 38.4kbps and 57.6kbps.
Parity and Stop bits
The parity and the stop bits can be chosen by modifying the
Holding Register 48
and the possible choices are:
0
No parity, 2 Stop Bits (default)
1
Odd parity, 1 Stop Bit
2
Even parity, 1 Stop Bit
The value of the Holding Registers is NOT coerced if trying to set a not allowed value.
When trying to enter a value in any holding register, the value is not overwritten if the new value is outside the load boundaries.
Содержание EC FAN FDP
Страница 2: ......