Rev. 0 - 11/12/2020
EC FAN
FDP
OPERATING MANUAL
Regal Beloit Italy S.p.A.
Via Modena, 18
24040 Ciserano (BG) ITALY
Phone +39 035 873 111
Fax +39 035 884 319
www.regalbeloit.com
Страница 1: ...Rev 0 11 12 2020 EC FAN FDP OPERATING MANUAL Regal Beloit Italy S p A Via Modena 18 24040 Ciserano BG ITALY Phone 39 035 873 111 Fax 39 035 884 319 www regalbeloit com ...
Страница 2: ......
Страница 3: ...IPTION 11 8 TECHNICAL FEATURES 12 8 1 Dimensional drawings 13 8 2 Motor driver connections 15 9 INSTALLATION 15 9 1 Commissioning 15 9 2 Operation 16 9 3 Ambient operating condition 16 9 4 Fan installation 16 9 5 Electrical connections 17 9 5 1 Power supply 18 9 5 2 Control board connection 18 9 5 3 Connection details 19 9 5 3 1 Analog 19 9 5 3 2 Modbus communication 21 9 5 3 3 Tachometric alarm a...
Страница 4: ...ation 27 12 2 Power limitation 27 12 3 Output current limitation 27 12 4 Input current limitation 27 13 OTHER VARIABLES 28 13 1 Bus voltage 28 13 2 Motor voltage 28 14 DERATING AND OVERHEATING PROTECTIONS 28 14 1 Driver overheating DERATING 28 14 2 Motor overheating THERMAL PROTECTOR 28 15 MASTER SLAVE MODE 29 15 1 Master and Slave 0 5V PWM out for 1 05 kW 1 phase only 29 16 COMMUNICATION 29 16 1 ...
Страница 5: ...he user of the potential personal damage that may result from an incorrect use of the machine or from the non compliance with the use and maintenance instructions Failure to comply with these safety messages could cause damage and or the partial or total destruction of the product or other equipment connected to it or harm people As to the NOTICE message the safety message does not indicate precis...
Страница 6: ...re the FDP fan is installed Before doing any maintenance make sure that the power supply and the batteries have been disconnected Install an all pole disconnecting device in the power supply system in accordance with IEC 60335 1 or IEC 60204 1 as applicable Conform to the wiring diagrams shown in the section ELECTRICAL CONNECTIONS of this manual The following warnings cautions and notes are provid...
Страница 7: ...hnical Service has repaired it Theinstaller and themaintenance man must know the content of this manual Although themain features of theequipment described in this manual are not subject to change the manufacturer reserves the right to modify the components details and accessories it deems necessary to improve the product or to meet manufacturing or commercial requirements at any time and without ...
Страница 8: ...t the fan in operation before the manufacturer of the machine has assessed and declared that the complete machine fulfils all the essential safety requirements set forth by the MD Please check the Declaration of Incorporation which accompanies each product or ask your Nicotra Gebhardt sales representative for additional information 2 1 Mechanical and electrical safety Single phase drive systems FD...
Страница 9: ...APACITOR VALUE WHEN PRESENT 11 MAXIMUM CURRENT INPUT 12 MOTOR RATED POWER 13 RATED RPM To improve the Electromagnetic compatibility a ferrite should be put on the power supply cable close to the driver The compliancy to the standards is intended for a single fan No tests have been made on multiple installations The EMC tests are conducted without 485 communication wire analog signals or Bluetooth ...
Страница 10: ...uction or since operating the fan for at least half an hour continuously The storage site shall have a temperature between 20 C and 70 C a Relative Humidity lower than 75 and not be subject to condensation or exposed to dust CAUTION CAUTION 5 PACKING CONTENTS 6xxxxx fdp xXx xxxx xxxXXX 12345 The fan is delivered in a cardboard box inside which there are the installation instructions and the option...
Страница 11: ... FD fans are normally co designed with our customer to provide the best integration of the fan in the structure of series produced machines Mounting plates are frequently used in vertical flow fan coil units also as condensation drainage collectors including a drain pipe connector The Fans of series FDP combine high energy efficiency and low noise level Thanks to the EC electronic commutation moto...
Страница 12: ...ong lists of inverter parameters Low sound level High reliability 8 TECHNICAL FEATURES Size Motor code Driver code Driver phases Abs curr A Abs pow W Min temp C Max temp C IP class protection 180 240 Z 1413G6 1431C1 1 Ph 2 81 A 641 W 20 C 40 C IP 32 200 190 N 1413G6 1431C1 1 Ph 2 65 A 621 W 20 C 40 C IP 32 200 190 N 1413H3 1431C1 1 Ph 4 63 A 1085 W 20 C 40 C IP 32 200 240 N 1413H4 1431C1 1 Ph 4 62...
Страница 13: ...0 OPERATING MANUAL OPERATING MANUAL EN EN 13 40 8 1 Dimensional drawings 6N4406 FDP 180 240 Z 1413G6 6N4407 FDP 200 190 N 1413G6 6N4408 FDP 200 190 N 1413H3 The plate dimensions and the anchor points can be different ...
Страница 14: ...Rev 0 11 12 2020 OPERATING MANUAL OPERATING MANUAL EN EN 14 40 6N4404 FDP 200 240 N 1413H4 6N4405 FDP 200 240 N 1413H3 6N4409 FDP 9 7A 1413H3 6N4410 FDP 9 9A 1413H3 ...
Страница 15: ...tent and qualified staff 9 1 Commissioning Work on the device system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material Only suitably qualified personnel trained in the setup installation commissioning and operation of the product should carry out work on the device system The FDP fan must be grounded through the PE connec...
Страница 16: ... Ambient operating conditions The installation place must be in accordance with the IP protection degree of the fan In this respect refer to the ID plate de scribed in chapter 3 Humidity Range 90 non condensing Altitude if the fan is to be installed at an altitude 1000m derating is required Shocks do not drop the fan or expose it to sudden shock Vibration do not install the fan in an area where it...
Страница 17: ... switch circuit breaker has been installed upstream the line and that it functions properly Work on the driver fan by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material Only suitably qualified personnel trained in the set up installation commissioning and operation of the product should carry out work on the driver fan This d...
Страница 18: ...ush in clamp suitable for 0 2 mm 24 AWG up to 2 5 mm 12 AWG stranded or 4 mm solid wire Use a bladed screwdriver 0 6x3 5 mm max to unlock As concerns the cable minimum section check the requirements issued by the country of installation Min and max section 0 13 1 31 mm2 26 16 AWG solid or stranded cable 9 5 2 Control board connection FDP 1 05kW 1 Phase 1 GND 2 IN 3 10V 4 GND 5 B 6 A 7 OUT TACHO OU...
Страница 19: ...nce to GND The analog input can accept also a PWM signal with f 1kHz WARNING WARNING Do not use devices having the signal GND connected to the NEUTRAL cable of the power supply The driver may be damaged or not functioning properly The available 10V power supply of the driver is intended to be used with a potentiometer of minimum 2KOhm with a max absorbed current of 5mA Any different devices connec...
Страница 20: ...ccurs when a fan is forced to run forward or backward rotation with a speed higher than 150 rpm If an ext 4 20mA device is used it is necessary to add 0 1 precision resistances between the ANALOG INPUT and GND The value of the resistance can range from 125 Ω Vsignal ranges from 0 5V to 2 5V to 500 Ω Vsignal ranges from 2V to 10V TACHO ALARM FILTER GND MODBUS B MODBUS A GND TRANSUCER INPUT ANALOG I...
Страница 21: ...RS 485 serial connection 2 With the driver powered off through an UART serial connection To connect OFFLINE the driver to a PC when the fan is powered off a USB to UART converter can be used K431A6 for 1 phase drivers A MOLEX connector 1 is used to connect the cable to the driver To connect the driver to a PC during the fan functioning a USB to 485 converter can be used K431F8 1 Specifications and...
Страница 22: ...ured by changing the value in Holding Register 46 see paragraph 16 3 at page 34 as a Digital Alarm Output refer to chapter 17 and paragraph 17 4 or in one of the alternative alarm modes described in pa ragraphs 11 1 and 11 2 Input Impedances Feature available on ANALOG INPUT 20 kΩ FDP 1 05 kW 1 Phase 9 5 3 4 Input Impedances 10 OPERATING MODES AND SETTING OPTIONS Depending on the fan model there a...
Страница 23: ...ead from the Input Register 14 For more details refer to the ANNEX Analog Signal Considerations The MAX and min speed default values are in function of the fan sizes 10 1 1 Analog speed control INPUT TYPE 0 Through this setting the fan runs at the speed defined by modifying the Holding Register 66 The setting is maintained meanwhile the fan is powered on and it is lost when the fan is powered off ...
Страница 24: ...d and speed therefore there could be some differences from each size The control is expressed in percentage instead of a defined measure unit The lower is the slip the higher is the performance and vice versa INPUT TYPE 8 Through this setting the fan emulates an ACIM motor and the slip is defined by modifying the Holding Register 66 The setting is maintained meanwhile the fan is powered on and it ...
Страница 25: ...nce is defined by modifying the Holding Register 66 The value of the reference is expressed in steps of 0 1 Volt therefore the register ranges from 0 to 100 The PID error is calculated in the following way Error ModbusREG_66 ANALOGInput 10 3 2 Modbus fixed ref PID closed control loop INPUT TYPE 11 In this mode the PID reference is defined by modifying the Holding Register 50 The value of the refer...
Страница 26: ... data are saved the fan follows the target corresponding to the analog value Analog Signal Temporary Setting The fan must stop waiting for a new register 66 value The fan must stop waiting for a new register 66 value Fixed Setting Analog Signal The fan must follow the target corresponding to the analog value at the inputs Fan is put in stop mode and after the data are saved the fan follows the tar...
Страница 27: ... stops and auto restarts after few seconds 12 SOA LIMITATIONS The speed limits can be adjusted for the signal rescaling but also to limit the noise in the final application The Input Register 2 indicates the Speed Reference minimum speed during alignment and dragging and the Set Speed in Closed Control Loop The Input Register 3 indicates the Measured Speed 12 1 Speed limitation The driver is set b...
Страница 28: ...ading the Input Register 15 If it is not possible to reach a steady thermal equilibrium the driver shuts down The protection acts limiting the current to the motor In this condition the driver goes in alarm see chapter 17 Once the temperature on the driver decreases under 75 C the alarm is automatically reset 14 1 Driver overheating DERATING The motor is protected through one or more Thermal Prote...
Страница 29: ... the fans in parallel are runnig in any speed control mode even if under control of a common external PID regulator TACHO ALARM FILTER TACHO ALARM FILTER GND GND MODBUS B MODBUS B MODBUS A MODBUS A GND GND TRANSUCER INPUT TRANSUCER INPUT ANALOG INPUT ANALOG INPUT ENABLE ENABLE 10V 10V 24V 24V GND GND IN IN 10 10 GND GND B B A A OUT OUT MASTER SLAVE MASTER SLAVE 16 COMMUNICATION Protocol interface ...
Страница 30: ...ed The alarm is indicated in the Input register 17 with the value of 255 0xFF Modbus Address The slave device address can be changed from value 1 to 247 by modifying the Holding Register 45 The default address from factory configuration is 1 RS 485 Default Communication Parameters 0 No Communication Timeout 1 to 32767 Time expressed in seconds therefore it is possible to set from 1sec to 9h 6m 8 s...
Страница 31: ...ding Register 34 is the Input Type related to the selection of the Operating Mode 0 Reset 1 Min Speed 2 Max Speed 7 Max Current 21 Fixed Speed Setting 30 Asynchronous Slip Setting 31 PID positive negative 32 Avoid Range Start 33 Avoid Range End 34 Input Type 36 Max Power Out 39 Constant Airflow Setting 42 Min Airflow 43 Max Airflow 45 Modbus Address 46 Tacho Alarm Filter 47 Modbus Baud rate 48 Mod...
Страница 32: ...be used to reduce the max motor current Allowed values 1 Default value Default value table below Although the value of the Max Current can be set at any value being lower than the original default one it is not recommended using a value that is 0 3 times below the default one 200 190 1413H3 200 240 1413H3 9 7 1413H3 9 9 1413H3 200 190 1413G6 180 240 1413G6 200 240 1413H4 1 05kW 1 Phase 1550 1550 1...
Страница 33: ...ault value 1 0 Modbus Speed Control The speed is set by modifying the register 66 1 Analog Speed Control The speed is set through the analog signal 2 Modbus Fixed Speed Control The speed is set by modifying the register 21 3 Master Slave The fan is configured as slave and follows the master 4 Analog Constant Airflow The constant airflow is set through the analog signal 5 Modbus Temporary Constant ...
Страница 34: ...t value 1 Holding Register 46 Tachometric Alarm Threshold Adim This register can be used to set the digital output function Allowed values table below Default value 0 The possible settings are 0 Tachometric The digital output indicates the measured speed through a PWM signal 1 Alarm The digital output indicates when an alarm occurs 2 Threshold The digital output indicates when the speed set in the...
Страница 35: ...ntrol Allowed values 0 32767 Default value 0 Holding Register 52 Ki Adim This register can be used to set the Integral Gain of the PID control Allowed values 0 32767 Default value 0 Holding Register 53 Kd Adim This register can be used to set the Derivative Gain of the PID control Allowed values 0 32767 Default value 0 Holding Register 54 Period ms This register can be used to set the time constan...
Страница 36: ...ates the rectified voltage after the PFC stage Input Register 10 Alarm 1 Adim This register must be combined with the Alarm2 register see the table in paragraph 17 2 Input Register 12 Motor Current mA This register indicates the peak value of the line current module To know the rms value it must be divided by 2 Input Register 13 Motor Voltage 10 1 V This register indicates the peak value of the ph...
Страница 37: ... This input indicates the Transducer Value The value must be multiplied by 10V 216 to have the corresponding voltage value Input Register 31 Measured Power W This register indicates the absorbed power Input Register 32 Input Current mA This input indicates the input absorbed current 16 5 Fan info and Modbus registers The Holding Register 44 indicates the fan model The Input Register 0 indicates th...
Страница 38: ...ter 10 and Input Register 17 are indicated 17 2 Modbus registers Alarm description Alarm 1 Alarm 2 Description Actions Type 0 0 Default operation No Errors No Actions ALARM 1 1 0 Memory error Blocking condition ALARM 2 2 0 Short Circuit Blocking condition ALARM 3 3 0 Loss of synchronism Auto restarting condition ALARM 4 4 1 Input Voltage outside range only with motor stopped Auto restarting condit...
Страница 39: ... Temporary Modbus mode it is necessary to reset the fan by setting the Holding Register 0 to value 1 instead of setting to 0 the Register 66 Temporary 0 5 8 11 Register 0 set to 1 The Holding Register 0 is a general reset and works also in the Analog mode and Fixed mode 18 AVAILABLE SOFTWARE A freeware software is available on Nicotra Gebhardt site http www nicotra gebhardt com for monitoring the ...
Страница 40: ...Rev 0 11 12 2020 OPERATING MANUAL OPERATING MANUAL EN EN 40 40 Regal Beloit Italy S p A Via Modena 18 24040 Ciserano BG ITALY Phone 39 035 873 111 Fax 39 035 884 319 www regalbeloit com ...