the  mechanical  stops,  therefore).  This  is  considered  as  an  obstacle  and
causes  an  inversion.  To  find  out  if  the  current  sensitivity  device  has
triggered,  count  how  many  times  the  Diagnostics  LED  flashes:  1  flash
indicates that the current sensitivity device triggered on account of motor
1, 2 flashes indicate that this was caused by motor 2.

6

FURTHER DETAILS: accessories

6.1 - Connecting a radio receiver

The control unit has a connector for fitting a 4 channel radio card complete
with SM slot. This remote control device functions by means of transmitters
which act on the inputs as per the following table:

8

PRODUCT MAINTENANCE

As the MC424 control unit is electronic it requires no particular maintenance.
However, at least every six months the efficiency of the entire system must
be checked according to the information described in chapter 3.

6.2 - Connecting model PS124 buffer battery

PS124 buffer batteries can be used to supply the control unit in case of net-
work blackouts. To install and connect the battery, proceed as shown in fig.
10.

DISPOSAL OF THE PRODUCT

6.3 - Connecting the Solemyo system

The control unit is designed to be powered  with the “Solemyo” photovoltaic
system  (photovoltaic  panel  and  24  V  battery).  To  connect  the  Solemyo
battery to the control unit, use the socket on the control unit that is normally
used for the buffer battery (see paragraph 6.2).

This product is an integral part of the automation, and therefore, they must
be disposed of together.

As  for  the  installation  operations,  at  the  end  of  the  life  of  this  product,  the
dis- mantling operations must be performed by qualified personnel.

This  product  is  made  from  different  types  of  materials:  some  can  be
recycled,  others  must  be  disposed  of.  Please  inform  yourselves  on  the
recycling  or  dis- posal  systems  provided  for  by  the  laws  in  force  in  your
area, for this category of product.

CAUTION! – some  parts  of  the  product  can contain  polluting  or  dangerous
substances which, if dispersed in the environment, may cause serious harm
to the environment and human health.

As  indicated  by  the  symbol  at  the  side,  it  is  forbidden  to
throw  this  product  into  domestic  refuse.  Therefore,  follow
the  “separated  collection”  instructions  for  disposal,
according to the methods provided for by local regulations
in  force,  or  redeliver  the  product  to  the  retailer  at  the
moment of pur- chase of a new, equivalent product.

CAUTION! – the  regulations  in  force  at  local  level  may  envisage  heavy
sanc- tions in case of abusive disposal of this product.

IMPORTANT!
- When the automation is powered by the “Solemyo” system, it MUST NOT
BE POWERED at the same time from the electrical mains.
- The Solemyo system can be used only if the Standby function on the con-
trol unit is ON and the connections are as shown in the diagram in fig. 5a.

7

TROUBLESHOOTING
(troubleshooting guide)

No LEDs are on:
•  Check whether the control unit is powered (measure a voltage of about

30Vdc at terminals 9-10 (or 24 Vdc with battery power).

• Check the 2 fuses, if not even the P1 Led is on or flashing a serious fault

has probably occurred and the control unit must therefore be replaced.

The P1 LED flashes regularly but the input LED’s L1, L2...L5 do not reflect
the state of the respective inputs
•  Switch the unit off for the moment in order to exit a possible programming

phase.

•  Carefully check the connections on terminals 11 to 16.

LED P1 flashes every 4 seconds
•  The control unit is in Stand by
status.
The “Automatic search” procedure does not start up
•    The  “Automatic  search”  procedure  only  starts  if  it  has  never  been

performed  before  or  if  the  memory  has  been  deleted.  To  check  whether
the memory is empty switch off the unit for a moment. When it is switched
on  again,  all  the  Leds  should  flash  rapidly  for  about  6  seconds.  If  they
only flash for 3 sec- onds, the memory already contains valid values. If a
new  “Automatic  search”  is  required,  the  memory  must  be  completely
deleted.

The “Automatic search” procedure has never been performed but it either
does not start or it behaves incorrectly
•  The system and all the safety devices must be operative in order to

activate the “Automatic search” procedure.

•  Make sure that no device connected to the inputs cuts in during the “Auto-

matic search” procedure.

•  In order for the “Automatic search” procedure to start correctly, the input

Leds must be on as shown in fig. 11, the P1 Led must flash once a

second.

The  “Automatic  search”  procedure  was  performed  correctly  but  the
manoeuvre does not start
•  Check that the safety device (STOP, PHOTO, PHOTO1 and, if installed,

PHOTO2)  Leds  are  on  and  that  the  relative  command Led  (STEP-BY-
STEP or AUX) remains on for the entire duration of the command.

•    If  the  “Phototest”  function  is  activated  but  the  photocells  do  not  function

cor- rectly,  the  DIAGNOSTICS  LED  indicates  the  fault  by  flashing  four
times.

The gate inverts the direction while moving
An inversion is caused by:
•    The  photocells  triggering  (PHOTO2  during  the  opening  manoeuvre,

PHOTO  or  PHOTO1  during  the  closing  manoeuvre).  In  this  case,  check
the photocell connections and input LEDs.

•  The current sensitivity device triggers while the motors are moving (not
near

E

N

Output Receiver

Control unit input

N° 1

Step by step

N° 2

AUX (reset value: Partially Open 1)

N° 3

“Open only”

N° 4

“Close only”

Содержание Moon MC424

Страница 1: ...Moon Vez rl s MC424 HU Egyszer s tett telep t i le r s...

Страница 2: ...knek fotocella vagy lv delem 1 x 0 5 mm2 14 PHOTO 1 NC kontaktusos bemenet biztons gi eszk z knek fotocella vagy lv delem 1 x 0 5 mm2 15 STEP BY STEP Input for cyclical functioning OPEN STOP CLOSE ST...

Страница 3: ...YIT LLJ Z R LLJ rendszerben m k dik El villog s Ha a funkci aktiv akkor gombnyom st k vet en bekapcsol a villog figyelmeztetve hogy nyilni fog a kapu de a motorok csak 3s m lva indulnak el Foto ut n b...

Страница 4: ...m sodpercig a program m dba val bel p st mind az 5db LED egyszerre t rt n felvill sa jelzi ezut n engedje el a gombokat P1 P2 3 s A P1 gomb ism telt megnyom s val l pkedhet nk az 5 v laszthat funkci k...

Страница 5: ...el bb P1 P2 3s PROGRAMOZ SI P LDA P1 x1 01 02 03 04 05 06 07 Nyomja le s tarsta lenyomva a P1 s P2 gombokat kb 3 m sodpercig a program m dba val bel p st mind az 5db LED egyszerre t rt n felvill sa je...

Страница 6: ...st Heavy Proportional On Photo Phototest Open P3 P3 SZ NET ID P2 P1 3 ig secs m sodperc P3 AUXILIARY BE 2 SZINT P1 Led P1 gyorsan villog type 1 type 2 only only Photo 2 P3 R FESZ T S P1 0 0 3 0 7 1 3...

Страница 7: ...en the automation is powered by the Solemyo system it MUST NOT BE POWERED at the same time from the electrical mains The Solemyo system can be used only if the Standby function on the con trol unit is...

Страница 8: ...ive 89 336 EEC DIRECTIVE 2004 108 EEC OF THE EUROPEAN PARLIAMENT AND COUNCIL of 15 December 2004 regard ing the approximation of member state legislation relating to electromagnetic compatibility repe...

Страница 9: ...1 3 8 4 7 7 6 6 2 HU E Jumper Az bra szerint jumperrel ll that melyik sz rny ny lik el sz r L N E F G H I L M L1 L5 P1 D P2 C P3 N B O A II 1 2 3 1 2 3 4 5 6 7 8 9 10 11 1213 1415 16 M1 M2 5 5 1 2...

Страница 10: ...3 232 mm 122 mm 205 4 5a HU Csatlakoztat s Stand by bekapcsolva energia takar kos m d III 310 mm 237 TX RX PHOTO2...

Страница 11: ...5b HU Csatlakoztat s stand by s fototeszt funkci n lk l 5c HU Csatlakoztat s Stand by n lk l fototeszt funkci val 6 IV TX RX TX RX...

Страница 12: ...sben 8 s 11 kapcsokra kell k tni 8 6 7 33 V max 5 W 12 V max 25 VA 6 7 NC 9a 9b 9c 11 11 11 NA NC NC 8 2K 8 2K 8 2K 12 12 12 HU Ha a Stand by act v akkor a 8 as s 11 kapcsokra kell k tni 9d 1 n 8 2K 2...

Страница 13: ...10 11...

Отзывы: