EN
6
– English
TABLE 7 - Second level functions
Input
Led
Parameter
Led
(level)
Value
Description
L1
Pause
Time
L1
5 seconds
Sets the pause time, namely the
time which lapses before auto-
matic closure. This will only take
effect if closing is active.
L2
15 seconds
L3
30 seconds
L4
45 seconds
L5
60 seconds
L6
80 seconds
L7
120 seconds
L8
180 seconds
L2
Step by
Step
function
L1
Open > Stop > Close > Stop > ...
Sets the sequence of commands
associated with the “Step-by-
Step”, “Open”, or “Close” inputs or
the radio control.
Note
– When setting L4, L5,
L7 and L8, the behaviour of the
“Open” and “Close” commands is
also modified.
L2
Open > Stop > Close > ...
L3
Open > Close > ...
L4
Apartment block:
• In the opening manoeuvre the “Step by Step” and “Open” commands have no effect; the “Close”
command causes the movement to be inverted, i.e. the closure of the leaf.
• In the closure manoeuvre the “Step by Step” and “Open” commands cause the movement to be
inverted, i.e. the leaf to open; the “Close” command has no effect.
L5
Apartment block 2:
• In the opening manoeuvre the “Step by Step” and “Open” commands have no effect; the “Close”
command causes the movement to be inverted, i.e. the closure of the leaf.
If the transmitted
command persists for more than 2 seconds, a “Stop” is performed.
• In the closure manoeuvre the “Step by Step” and “Open” commands cause the movement to be
inverted, i.e. the leaf to open; the “Close” command has no effect.
If the transmitted command
persists for more than 2 seconds, a “Stop” is performed.
L6
Step-by-step 2:
less than 2 seconds generates “Partial opening”.
L7
Hold-to-run:
the manoeuvre is performed only if the transmitted command persists; if the command
is interrupted the manoeuvre stops.
L8
Opening in “semi-automatic mode”, closing in “hold-to-run mode”.
L3
Motor
speed
L1
Very slow
Sets the motor speed during nor-
mal travel.
L2
Slow
L3
Medium
L4
Fast
L5
Very fast
L6
Extremely fast
L7
Fast opening (L4), Slow Closing (L2)
L8
Extremely fast Opening (L6), Medium Closing (L3)
L4
Motor
discharge
after closing
L1
No discharge
Sets duration of “short inversion”
of bo th motors after performing
Close ma noeuvre with the aim of
reducing the final residual thrust.
L2
Level 1 - Minimum discharge (about 100 ms)
L3
Level 2 - ...
L4
Level 3 - ...
L5
Level 4 - ...
L6
Level 5 - ...
L7
Level 6 - ...
L8
Level 7 - Maximum discharge (about 800 ms)
L5
Motor
force
L1
Level 1 - Minimum force
Adjusts the force of both motors.
L2
Level 2 - ...
L3
Level 3 - ...
L4
Level 4 - ...
L5
Level 5 - ...
L6
Level 6 - ...
L7
Level 7 - ...
L8
Level 8 - Maximum force
L6
Pedestrian
or partial
opening
L1
Pedestrian 1 (opening of leaf M2 to 1/4 of total opening)
Sets type of opening associated
with “Partial open 1” command.
In levels L5, L6, L7, L8; “mini-
mum” opening means the smaller
opening out of M1 and M2; for
example, if M1 opens to 90° and
M2 opens to 110°, the minimum
opening is 90°.
L2
Pedestrian 1 (opening of leaf M2 to 1/2 of total opening)
L3
Pedestrian 3 (opening of leaf M2 to 3/4 of total opening)
L4
Pedestrian 4 (Complete opening of leaf 2)
L5
Partial 1 (opening of two leafs to 1/4 of “minimum” opening)
L6
Partial 2 (opening of two leafs to 1/2 of “minimum” opening)
L7
Partial 3 (opening of two leafs to 3/4 of “minimum” opening)
L8
Partial 4 (opening of two leafs to “minimum” opening)
L7
Maintenance
warning
L1
500
Controls the number of manoeu-
vres: when this number is ex-
ceeded, the control unit signals an
automation maintenance request;
see paragraph 5.3.2. – Mainte-
nance warning.
L2
1.000
L3
1.500
L4
2.500
L5
5.000
L6
10.000
L7
15.000
L8
20.000
L8
List of
faults
L1
Manoeuvre 1 result (most recent)
The type of fault that has occurred
in the last 8 manoeuvres can be
established.
See TABLE 12 – Fault log.
L2
Manoeuvre 2 result
L3
Manoeuvre 3 result
L4
Manoeuvre 4 result
L5
Manoeuvre 5 result
L6
Manoeuvre 6 result
L7
Manoeuvre 7 result
L8
Manoeuvre 8 result
Note
– The factory settings are highlighted in grey.