40
NIBE VVM 300
Miscellaneous
9.1.0 Heat pump settings
Settings for the air/water heat pump are made from the
sub-menus in this menu.
Menu 9.1.1 Heat p. start value
Degree minute setting for start of heat pump.
The value can be set between -120 and 0. The factory set-
ting is -60.
Menu 9.1.2 Number of heat pumps
The number of connected heat pumps are indicated here.
The value can be set between 0 and 1.
The factory setting is 1.
Menu 9.1.3 Start defrost(06)
The desired start temperature on the evaporator sensor for
heat pump defrosting is set here.
Menu 9.1.4 Stop defrost(07)
The desired stop temperature on the evaporator sensor for
heat pump defrosting is set here.
Menu 9.1.5 Max defrost time(09)*
The longest period for defrosting the heat pump is set
here.
Menu 9.1.6 Time betw. defr(10)*
Minimum running time, heat production before new de-
frosting is permitted in the heat pump.
* See Installation and Maintenance Instructions for FIGHTER 2020 for setting range and factory settings.
Menu explanation
Menu 8.4.2 Pool temperature
Current pool temperature is displayed here.
Menu 8.4.3 Pool start temp.
The temperature at which pool heating is to start is shown
here. When the temperature drops below this value, heat-
ing starts after the hot water and heating demands are
met.
The value can be adjusted between 5 and 40 °C in incre-
ments of 0.5 °C.
The factory setting is 25 °C.
Menu 8.4.4 Pool stop temp.
The temperature at which pool heating is to stop.
The value can be adjusted between 5 and 40 °C in incre-
ments of 0.5 °C.
The factory setting is 28 °C.
Menu 8.4.5 Return
Return to menu 8.4.0.
Menu 8.5.0 Period settings
Time periods for heating and hot water production are set
in the sub-menus for this menu.
Menu 8.5.1 Period time
The length of time for production of hot water and heating
is set here.
The value is adjustable between 5 and 60 minutes. The fac-
tory setting is 60 minutes.
Menu 8.5.2 Max time for HW
Here you select how much time of the period time (menu
8.5.1) is to be used to heat the hot water when there is a
need of both heating and hot water.
The value is adjustable between 0 and 60 minutes. The fac-
tory setting is 30 minutes.
Menu 8.5.3 Return
Return to menu 8.5.0.
Menu 8.6 Return
Return to menu 8.0.
Содержание NIBE VVM 300
Страница 2: ...LEK LEK 1 2 LEK LEK 3 4 5...
Страница 46: ...44 NIBE VVM 300 Miscellaneous Electrical circuit diagram Electrical circuit diagram...
Страница 47: ...45 NIBE VVM 300 Miscellaneous Electrical circuit diagram...
Страница 48: ...46 NIBE VVM 300 Miscellaneous Electrical circuit diagram...
Страница 49: ...47 NIBE VVM 300 Miscellaneous Electrical circuit diagram...
Страница 50: ...48 NIBE VVM 300 Miscellaneous Electrical circuit diagram...
Страница 57: ...55 NIBE VVM 300...
Страница 58: ...56 NIBE VVM 300...
Страница 59: ......