Program setting of ERS 10 can be performed via the start
guide or directly in the menu system in the main product.
Caution
See the documentation for the main product.
Start guide
The start guide appears upon first start-up after heat
pump installation, but is also found in menu 5.7.
Menu system
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 5.2.4 -system settings
Activating/deactivating of accessories.
Activate: "exhaust/supply air module".
Menu 5.3.12 - exhaust/supply air module
Settings specific to ERS 10.
"Lowest extract air temp.": Set the minimum extract air
temperature to prevent the heat exchanger freezing.
The supply air fan speed reduces if the extract air tem-
perature at (BT21) is lower than the set value.
"Bypass at temperature": If a room sensor is installed, set
the over-temperature at which the bypass damper
(QN37) must open here.
"Months btwn filter alarms": Set how often the filter
alarm must be displayed.
TIP
When ERS 10 is activated, the other ventilation
menus will also light up.
15
Chapter 7 |
Program settings
NIBE™ ERS 10-500