Dimensions and pipe
connections
900
44
600
4 x Ø160
Ø32
308
146
146
278
188
146
612
32
Mounting
When hanging on a wooden wall, a vibration damper is
recommended to prevent vibration being transferred.
1. Install the enclosed bracket to the wall.
2. Install ERS 10 on the brackets.
L
EK
LEK
Condensation water drain
ERS 10 can produce several litres of condensation water
per day. It is therefore important that the condensation
drain is correctly laid out and the unit is installed level.
Check that the water seal is airtight and firmly in position.
The connection must be made so that the user can check
that the water seal is functioning, without opening ERS
10.
Installation from the water seal and forward to the drain
must be carried out with a necessary fall of 1 %. If the
unit is installed in a cold area, the condensation water
drain pipe must be insulated so that the condensation
water in the pipe does not freeze. It is also recommended
that the water seal is mounted in a heated area to
guarantee that the water in the water seal does not
freeze.
If it cannot be guaranteed that insulation will protect
the condensation water drain pipe against frost, a ther-
mostat controlled heating cable must be installed around
the condensation water drain pipe.
NOTE
During operation there is a negative pressure
in the unit which means that a water column of
at least 100 mm must be guaranteed in the
water seal.
1
0
0
NIBE™ ERS 10-500
Chapter 4 |
Pipe and ventilation connections
10
4 Pipe and ventilation connections