General ventilation
connections

• Ventilation installation must be carried out in accord-

ance with current norms and directives.

• Connections must be made via flexible hoses, which

should be installed so that they are easy to replace.

• Provision must be made for inspection and cleaning

of the duct.

• Make sure that there are no reductions of cross-sec-

tional area in the form of creases, tight bends, etc.,
since this will reduce the ventilation capacity.

• The air duct system must be a minimum of air tight-

ness class B.

• To prevent fan noise being transferred to the ventila-

tion devices, silencers should be installed in the duct
system. In the event of ventilation devices in noise-
sensitive rooms, silencers must be installed.

• The extract air and outdoor air ducts are insulated us-

ing diffusion-proof material (at least PE30 or equival-
ent) along their entire lengths.

• Ensure that the condensation insulation is fully sealed

at any joints and/or at lead-in nipples, silencers, roof
cowls or similar.

• The air must be routed to the outdoor air duct through

an outer wall grille in the facade. The outer wall grille
must be installed so that it is protected from the
weather and must be designed so that no rainwater
and/or snow can penetrate the facade or follow the
air into the duct.

• When positioning the outdoor air and extract air

hood/grille, bear in mind that the two air flows must
not short circuit to prevent the extract air from being
drawn into ERS 10 again.

• A duct in a masonry chimney stack must not be used

for extract air or outdoor air.

NOTE

To ensure a sealed connection to ERS 10, the
supplied hose clips must be used for connect-
ing the air ducts.

EXHAUST AIR DUCT /KITCHEN FAN

Exhaust air duct (kitchen fan) must not be connected to
ERS 10.

To prevent food vapour being transferred to ERS 10 the
distance between the kitchen fan and the exhaust air
device must be considered. The distance should not be
less than 1.5 m, but this can vary between different in-
stallations.

Always use a kitchen fan when cooking.

Ventilation flow

Connect ERS 10 so that all the exhaust air, except kit-
chen duct air (kitchen fan), passes through the heat ex-
changer (EP26) in the product.

The ventilation flow must comply with the applicable
national standards.

The supply air flow must be lower than the exhaust air
flow to prevent over pressure in the house.

Set the ventilation capacity in the main product’s menu
system (menu 5.1.5).

Adjusting ventilation

To obtain the necessary air exchange in every room of
the house, the exhaust air valve and the supply air inlet
as well as the fans in the ventilation heat exchanger
must be correctly positioned and adjusted.

Immediately after installation adjust the ventilation so
that it is set according to the projected value of the
house.

Incorrect adjustment of the ventilation may lead to re-
duced installation efficiency and thus poorer operating
economy, and may cause moisture damage in the
building

Dimension and
ventilation
connections

900

44 

600

4 x Ø160

G32

308

146

146

278

188

146

612

Exhaust air

Outdoor air

Extract air

Supply air

NIBE ERS 10-400

Chapter 4 | Pipe and ventilation connections

12

Содержание ERS 10-400

Страница 1: ...IHB EN 1948 1 531749 INSTALLER MANUAL Ventilation heat exchanger NIBE ERS 10 400 LEK...

Страница 2: ......

Страница 3: ...ain 12 General ventilation connections 12 Ventilation flow 12 Adjusting ventilation 12 Dimension and ventilation connections 13 Preheating the outdoor air 14 5 Electrical connection 14 Connecting to m...

Страница 4: ...supervision Rights to make any design or technical modifications are reserved NIBE 2019 SYMBOLS NOTE This symbol indicates danger to person or ma chine Caution This symbol indicates important informat...

Страница 5: ...uction of the product No special tools are required for access Improper disposal of the product by the user results in administrative penalties in accordance with current le gislation Inspection of th...

Страница 6: ...r the unit is located walls to sound sensitive rooms should be fitted with sound insulation Condensation comes from the underside of the vent ilation heat exchanger Condensation outlet with water seal...

Страница 7: ...ll the hatch towards yourself LEK Removing parts of the insulation FRONT INSULATION The insulation in the front must be removed to access the internal parts 1 Remove the air filter 2 Slacken off the s...

Страница 8: ...LEK GQ2 XL31 XL34 XL32 XL33 AA5 GQ3 WM5 EP26 XL40 HQ11 HQ10 UB1 QN37 W2 W1 NIBE ERS 10 400 Chapter 3 The ventilation heat exchanger design 8 3 The ventilation heat exchanger design...

Страница 9: ...Temperature sensor supply air BT22 Temperature sensor outdoor air BT23 Electrical components Accessory card AA5 Cable gland UB1 Cord with connection plug W1 Communication cable W2 Ventilation Heat ex...

Страница 10: ...hanging on a wooden wall a vibration damper is recommended to prevent vibration being transferred 1 Install the enclosed bracket to the wall 2 Install ERS 10 on the brackets LEK LEK NIBE ERS 10 400 C...

Страница 11: ...e carried out with an essential fall of 1 If the ventilation heat exchanger is installed in a cold area the condensation water drain pipe must be insulated so that the condensation water in the pipe d...

Страница 12: ...in a masonry chimney stack must not be used for extract air or outdoor air NOTE To ensure a sealed connection to ERS 10 the supplied hose clips must be used for connect ing the air ducts EXHAUST AIR...

Страница 13: ...oo often in areas with colder climates an electrical air heater EAH EB17 and an outdoor air sensor BT23 should be installed in the outdoor air duct as illustrated EAH heats the incoming outdoor air so...

Страница 14: ...trical wiring diagram see page 23 Connecting to main product If several accessories are to be connected or are already connected the following cards must be connected in series with the previous card...

Страница 15: ...Manual for the location of the input board AA3 The DIP switch AA5 S2 must be set as follows ON 1 2 3 4 5 6 7 8 ERS 10 no 2 ON 1 2 3 4 5 6 7 8 ERS 10 no 1 ON 1 2 3 4 5 6 7 8 ERS 10 no 4 ON 1 2 3 4 5 6...

Страница 16: ...red and permitted Caution An incorrectly set ventilation flow can damage the house and may also increase energy con sumption NOTE Order a ventilation adjustment to complete the setting Ventilation cap...

Страница 17: ...of accessories Activate exhaust supply air module MENU 5 3 12 EXHAUST SUPPLY AIR MODULE Settings specific to ERS 10 Lowest extract air temp Set the minimum extract air temperature to prevent the heat...

Страница 18: ...red light is still visible and a menu called alarm is visible in the display the problem that caused the alarm remains If the alarm disappears and then returns see the troubleshooting section page 18...

Страница 19: ...RACTING VENTILATION Filter blocked Clean or replace the filter The ventilation is not adjusted Order implement ventilation adjustment Closed too much choke or blocked ventilation device Check and clea...

Страница 20: ...reezing Used mainly in colder climates Part no 067 603 TOP CABINET Top cabinet that conceals the ventilation ducts and re duces the sound to the installation room Height 345 mm Part no 089 757 Height...

Страница 21: ...Dimensions 900 44 600 4 x 160 G32 308 146 146 278 188 146 612 21 Chapter 10 Technical data NIBE ERS 10 400 10 Technical data...

Страница 22: ...tional Declared typology Variable speed drive Type of drive Recuperative Type of heat recovery system 86 Thermal efficiency of heat recovery 394 m3 h Maximum air flow rate 163 W Electric power input o...

Страница 23: ...ecification Sheet 051145 1 Page 2 2 Created 2018 11 06 12 02 0 001 MJN 2018 11 06 Production GBN 2016 04 27 WIRING DIAGRAM ERS 10 400 ELSCHEMA ERS 10 400 051145 1 23 Chapter 10 Technical data NIBE ERS...

Страница 24: ...on 5 M Manage alarm 18 Marking 4 P Pipe and ventilation connections Exhaust air duct 12 S Safety information Inspection of the installation 5 Marking 4 Symbols 4 Symbols on ERS 10 4 Start up and inspe...

Страница 25: ......

Страница 26: ......

Страница 27: ...nibe fi NORWAY NETHERLANDS GREAT BRITAIN ABK AS Brobekkveien 80 0582 Oslo Tel 47 23 17 05 20 post abkklima no nibe no NIBE Energietechniek B V Energieweg 31 4906 CG Oosterhout Tel 31 0 168 47 77 22 i...

Страница 28: ...NIBE Energy Systems All product illustrations facts and data are based on the available information at the time of the publication s approval NIBE Energy Systems makes reservations for any factual or...

Отзывы: