Tranquility
®
Fluid Cooler – 60 Hz
R e v. : F e b r u a r y 2 2 , 2 0 2 2
c l i m a t e m a s t e r.c o m
23
Electrical – Line Voltage
⚠
WARNING!
⚠
⚠
CAUTION!
⚠
Electrical - Line Voltage
All field installed wiring, including electrical ground,
must comply with the National Electrical Code as well
as all applicable local codes. Refer to the unit electrical
data for fuse sizes. Consult wiring diagram for field
connections that must be made by the installing (or
electrical) contractor.
Electrical disconnect must be capable of electrically
de-energizing all power bearing conductors feeding the
TFC unit.
All final electrical connections must be made with a
length of flexible conduit to minimize vibration and
sound transmission to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and
phase shown on the unit serial plate. Line and low
voltage wiring must be done in accordance with local
codes or the National Electric Code, whichever is
applicable.
Power Connection
Line voltage connection is made by connecting the
incoming line voltage wires to the “L” side of the power
distribution block as shown in Figure 12. Consult Table
5a and 5b for electrical ratings and maximum fuse size.
208/230 Volt Operation
Verify transformer tap with unit wiring diagram to
ensure that the transformer tap is set to the correct
voltage, 208V or 230V.
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 5a: TFC with Flow Switch
Model
Fan Motor
FLA
Total Unit
FLA
Min Circuit
AMP
Max
Fuse/HACR
036
2.2
2.2
2.8
15A
060
1.0
1.3
1.3
15A
Rated Voltage of 208/230/60/1
Min/Max Voltage of 197/252
All fuses Class RK-5
Table 5b: TFC with Internal Pump
Model
Fan Motor
FLA
Loop
Pump FLA
Total Unit
FLA
Min Circuit
AMP
Max
Fuse/HACR
036
2.2
1.4
3.6
4.2
15A
060
1.0
1.4
2.4
2.7
15A
Rated Voltage of 208/230/60/1
Min/Max Voltage of 197/252
All fuses Class RK-5