Nibe CLIMATEMASTER Tranquility TFC 036 Скачать руководство пользователя страница 16

Tranquility

®

 Fluid Cooler – 60 Hz

R e v. :   F e b r u a r y   2 2 ,   2 0 2 2

G e o t h e r m a l   H e a t i n g   a n d   Co o l i n g

16

Loop Antifreeze Protection

Antifreeze Selection - General

Antifreeze is required if the system can be subjected to 

ambient temperatures below 35°F. Alcohols and glycols 

are commonly used as antifreeze solutions. Your local 

representative should be consulted for the antifreeze best 

suited to your area. In the event of a power outage, freeze 

protection should be maintain in the system to the lowest 

subjected ambient conditions.

Initially calculate the total volume of fluid in the piping 

system using Table 2. Then use the percentage by 

volume shown in Table 3 for the amount of antifreeze. If 

the minimum ambient temperature that can be reached 

is less than shown in Table 3 please contact your local 

representative for the appropriate percentage to protect 

the system. Antifreeze concentration should be checked 

from a well mixed sample using a hydrometer to measure 

specific gravity.

Table 2: Fluid Volume

 WARNING! 

Fluid Volume (gal [liters] per 100’ [30 meters] Pipe)

Pipe

Size

Volume (gal) [liters]

Copper

1”

4.1 [15.3]

1.25”

6.4 [23.8]

2.5”

9.2 [34.3]

Polyethylene

3/4” IPS SDR11

2.8 [10.4]

1” IPS SDR11

4.5 [16.7]

1.25” IPS SDR11

8.0 [29.8]

1.5” IPS SDR11

10.9 [40.7]

2” IPS SDR11

18.0 [67.0]

Fluid Cooler

036/060

7.4 [28]

Flush Cart Tank

10” Dia x 3ft tall 

[25.4cm x 91.4cm tall]

10 [37.9]

Table 3: Antifreeze Percentages by Volume

Type

Minimum Temperature  

for Low Temperature Protection

10°F 

[-12.2°C]

15°F 

[-9.4°C]

20°F 

[-6.7°C]

25°F 

[-3.9°C]

Methanol

Propylene Glycol

Ethanol*

21%

29%

23%

17%

24%

20%

13%

18%

16%

8%

12%

11%

* Must not be denatured with any petroleum based product

WARNING!

 Always dilute alcohols with water (at least 50% 

solution) before using. Alcohol fumes are flammable and 

can cause serious injury or death if not handled properly.

When handling methanol (or any alcohol), always wear 

eye protection and rubber gloves as alcohols are easily 

absorbed through the skin.

Contact your ClimateMaster distributor if you have any 

questions as to antifreeze selection.

 WARNING! 

 CAUTION! 

WARNING!

 Always use properly marked vehicles (D.O.T. 

placards), and clean/suitable/properly identified containers 

for handling flammable antifreeze mixtures. Post and 

advise those on the jobsite of chemical use and potential 

dangers of handling and storage.

NOTICE:

 DO NOT use automotive windshield washer fluid as 

antifreeze. Washer fluid contains chemicals that will cause 

foaming.

CAUTION!

 Always obtain MSDS safety sheets for all 

chemicals used in ground loop applications including 

chemicals used as antifreeze.

Antifreeze Charging

It is highly recommended to utilize premixed antifreeze 

fluid where possible to alleviate many installation 

problems and extra labor. 

The following procedure is based upon pure antifreeze 

and can be implemented during the Full Flush procedure 

with three way valves in the Figure 10c - Valve Position 

C. If a premixed mixture of 15°F [-9.4°C] freeze protection 

is used, the system can be filled and flushed with the 

premix directly to prevent handling pure antifreeze during 

the installation.

1.  Flush loop until all air has been purged from system 

and pressurize to check for leaks before adding  

any antifreeze.

2.  Run discharge line to a drain and hook up antifreeze 

drum to suction side of pump (if not adding below 

water level through approved container). Drain flush 

cart reservoir down to pump suction inlet so reservoir 

can accept the volume of antifreeze to be added.

3. 

Calculate the amount of antifreeze required by first 

calculating the total fluid volume of the loop from 

Table 2. Then calculate the amount of antifreeze 

needed using Table 3 for the appropriate freeze 

protection level. Many southern applications require 

freeze protection because of exposed piping to 

ambient conditions.

4. 

Isolate unit and prepare to flush only through loop (see 

Figure 10a). Start flush cart, and gradually introduce 

the required amount of liquid to the flush cart tank 

(always introduce alcohols under water or use suction 

of pump to draw in directly to prevent fuming) until 

attaining the proper antifreeze protection. The rise 

Содержание CLIMATEMASTER Tranquility TFC 036

Страница 1: ...p Antifreeze Protection 16 17 Optional Internal Pump 18 Water Quality Standards 19 20 Earth Ground Resistance Measurement 21 Electrolysis Voltage and Current 22 Electrical Line Voltage 23 Electrical Field Wiring Installation 24 Electrical Low Voltage Wiring 25 DIP Switch Settings 25 AXM Controls 26 TFC with Pump Wiring Diagram 27 TFC with Flow Switch Wiring Diagram 28 Unit Starting and Operating C...

Страница 2: ...Tranquility Fluid Cooler 60 Hz Rev Feb ru ar y 22 2022 Geothermal Heating and Cooling 2 This page intentionally left blank ...

Страница 3: ... 10 11 12 13 14 036 UNIT SIZE 060 VOLTAGE CONTROLS REVISION LEVEL Future Pump Options Future T 1 T Tranquility SERIES FC 3 FC Fluid Cooler CONFIGURATION Heat Exchanger Options S 15 S Standard Standard 2 Standard High Head Pump with Check Valve C Flow Switch N NOT APPLICABLE Future N NOT APPLICABLE A A Ecoated UV COAT B Standard N NOT APPLICABLE Outdoor G 208 230 60 1 2 ...

Страница 4: ... avoid equipment damage DO NOT use these units as a source of heating or cooling during the construction process The mechanical components and filters can quickly become clogged with construction dirt and debris which may cause system damage and void product warranty WARNING WARNING This product can expose you to chemicals including Carbon Black which is known to the State of California to cause c...

Страница 5: ... Equipment should be stored in its original packaging in a clean dry area Store units in an upright position at all times Stack units a maximum of 2 units high Unit Protection Cover units on the job site with either the original packaging or an equivalent protective covering Cap the open ends of pipes stored on the job site In areas where painting plastering and or spraying has not been completed ...

Страница 6: ...al Fan Motor Fan Size in 20 25 Water Connection Size FPT in 1 Swivel Air Coil Dimensions H x W 35 x 29 Rows 3 FPI 12 Weights Operating lbs kg 304 138 315 143 Packaged lbs kg 349 158 360 163 Total Fluid Volume gal L 7 4 28 Unit Maximum Water Working Pressure Max Pressure PSIG kPa Pump Option 145 1000 Flow Switch Option 160 1103 ...

Страница 7: ...mensional Data A B TOP VIEW E C F FRONT VIEW 13 4 7 9 15 3 3 5 BOTTOM VIEW Model Overall Cabinet Electrical Knockouts A B C E F Width Depth Height 1 2 3 4 036 in 36 5 36 5 44 1 12 1 14 3 cm 92 7 92 7 112 0 30 7 36 3 060 in 36 5 36 5 45 9 12 1 14 3 cm 92 7 92 7 116 6 30 7 36 3 ...

Страница 8: ...these applications The first option has an internal flow switch inside the unit to validate flow in the system The water source heat pump will contain a pump to circulate fluid throughout the system when a call is given from an indoor thermostat The second option provides an internal pump in the TFC in installations where the water source heat pump does not have a circulator As water circulates in...

Страница 9: ...nual heat rejection and not for peak temperature reduction For instance if a hot loop condition is present in the system most of the annual rejection by the fluid cooler occurs during fall winter and spring This means the unit will be operating in space heating and the warmest water in the system would then be leaving the ground loop and returning to the unit 2 Parallel The fluid cooler is install...

Страница 10: ...n the fluid cooler is installed in parallel with the water source heat pump The biggest change is the fluid cooler now requires the internal pump option and is now piped so the outlet of the fluid cooler and heat pump is on a common line The fluid cooler monitors a signal from the heat pump and will turn on the circulating pump If conditions are favorable for heat rejection the fan runs at the app...

Страница 11: ... aid in avoiding potential future damage to the installation Unit Location Locate the unit in an outdoor area that allows for adequate access for loop installation and also has appropriate space for service personnel to perform typical maintenance and repairs The unit should be located away from buildings landscaping and other units by the dimensions given in Figure 5 Installation within six feet ...

Страница 12: ...loop piping materials should be polyethylene fusion only for in ground sections of the loop and it is also recommended for inside piping Galvanized or steel fittings should not be used at any time due to their tendency to corrode All plastic to metal threaded fittings should be avoided due to their potential to leak over time The earth loop piping should be brought through the loop access holes in...

Страница 13: ...d be used during the flushing process to ensure all debris is removed See Table 1 to determine the flow rate required to attain 2 fps 0 6 m s The TFC requires a minimum flow rate of 16 gpm 60 6 l m to achieve 2 fps The steps below must be followed to ensure proper flushing Units with internal variable speed pumps also include a check valve internal to the pump It is not possible to flush backwards...

Страница 14: ... Open the valve back up and a pressure surge will be sent through the loop which forces air out of the piping system Notice the drop in the fluid level in the flush cart tank If all air is purged from the system the level will only drop 3 8 in 10 diameter PVC flush tank approximately 0 5 gallon 1 9 liters If the level drops more than this flushing should continue until all air is removed from the ...

Страница 15: ...d 75psi 345 to 517 kPa upon completion of flushing pressure should be sufficient for all seasons Unhook the flush cart from the fluid cooler Install caps on the fluid cooler water inlet and outlet to prevent and leaks Figure 9d Valve Position D Pressurize and Operation Out In Valve Position 2 Close to isolate Internal Flow Controller 3 Close Internal Flow Controller Valves for Operation Mode From ...

Страница 16: ...mateMaster distributor if you have any questions as to antifreeze selection WARNING CAUTION WARNING Always use properly marked vehicles D O T placards and clean suitable properly identified containers for handling flammable antifreeze mixtures Post and advise those on the jobsite of chemical use and potential dangers of handling and storage NOTICE DO NOT use automotive windshield washer fluid as a...

Страница 17: ...te the level of freeze protection Do not antifreeze more than a 10 F 12 2 C freeze point Specific gravity hydrometers are available in the residential price list Repeat after reopening and flushing for a minute to ensure good second sample of fluid Inadequate antifreeze protection can cause nuisance low temperature lockouts during cold weather 7 Close the flush cart return valve immediately therea...

Страница 18: ...d Flow gpm With Check Valve Figure 11 High Head Variable Pump Performance Determine overall system pressure drop and compare to Figure 11 to ensure that adequate fluid flow can be provided Unit pressure drop is shown on the Performance Pressure Drop pages of this manual Note If head pressure required exceeds pump capacity then a external pump may be required ...

Страница 19: ...c a B Sulfate reducing 0 0 0 0 L m s l l e c a i r e t c a b Suspended Solidsβ 0 1 0 1 0 1 0 1 m p p S S T Earth Ground Resistanceχ 0 s m h O Consult NEC local electrical codes for grounding requirements Electrolysis Voltageδ 0 0 3 V m Measure voltage internal water loop to HP ground Leakage Currentδ 5 1 A m Measure current in water loop pipe Building Primary Electrical Ground to unit must meet lo...

Страница 20: ...uld not be used 7 If water temperature is expected to fall below 40 F antifreeze is required Refer to the heat pump IOM for the correct solution ratios to prevent freezing α Hydrogen Sulfide has an odor of rotten eggs If one detects this smell a test for H2S must be performed If H2S is detected above the limit indicated remediation is necessary Consult with your Water Testing Treatment Professiona...

Страница 21: ...e measured should be zero Ohms The NEC allows a resistance to ground up to 20 Ohms Any resistance above zero indicates a poor earth ground which may be the result of a hot neutral line or that conduc ve water is present Both of these may lead to electrolysis and corrosion of the heat pump piping A check for both should be performed and resolved Note if the well casing is plas c a conduc ve path ca...

Страница 22: ...an 500mV electrolysis will occur and corrosion will result If voltage is measured the cause is a high resistance earth ground or current on the neutral conductor Remedial measures should be performed Measure the current flowing through the piping system by using an amp clamp probe on the water in line The HP must be opera ng and the water stream flowing There should be zero amps measured If current ...

Страница 23: ...e Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the L side of the power distribution block as shown in Figure 12 Consult Table 5a and 5b for electrical ratings and maximum fuse size 208 230 Volt Operation Verify transformer tap with unit wiring diagram to ensure that the transformer tap is set to the correct voltage 208V or 230V WARNING To avoid ...

Страница 24: ... y 22 2022 Geothermal Heating and Cooling 24 Electrical Field Wiring Installation Figure 12 Control Wiring Control Board Dashed lines represent field wiring Dashed lines represent field wiring Refer to Data Plate Use copper conductors only Ground ...

Страница 25: ...trol pump and fan operation Unit configuration setting are set at the factory for unit size and pump option The dip switch setting are shown in Table 6 Figure 13 Control Board Control Board Table 6 Dip Switch Settings S1 Dip Switch On Off S1 1 Hybrid Operation Stand Alone Operation S1 2 Pump Option Flow Switch Option S1 3 TFC036 TFC060 S1 4 N A N A ...

Страница 26: ...d into the ON position the unit will operate with logic to operate the fan in high speed when 1 The EAT is greater than 40 F when the freeze protection is set for water or 25 F when set for antifreeze and 2 The temperature difference EWT EAT must be greater than 2 F and 3 The EWT is greater than 45 F and 4 The flow switch input W is closed with a flow switch option or there is the presence of a Y1...

Страница 27: ...Tranquility Fluid Cooler 60 Hz Rev Februar y 22 2022 climatemaster com 27 TFC with Pump Wiring Diagram 96B0077N01 ...

Страница 28: ...Tranquility Fluid Cooler 60 Hz Rev Feb ru ar y 22 2022 Geothermal Heating and Cooling 28 TFC with Flow Switch Wiring Diagram 96B0077N02 ...

Страница 29: ... that controller field selection options are properly set Refer to unit wiring diagram Service access panels are in place SYSTEM CHECKOUT System water temperature Check water temperature for proper range System pH Check and adjust water pH if necessary to maintain a proper level Proper pH promotes system longevity see Table 4 System flushing Verify that all air is purged from the system Air in the...

Страница 30: ... the lower voltage of dual voltage rated units Heat Rejection Capacity Air Temp Entering Fluid Cooler DB Air ΔT Water Flow Rate Water Temp Entering Fluid Cooler Water ΔT through Fluid Cooler Approach Temp Fan Power BTUH F F GPM F F F Watts 28900 70 10 9 85 6 9 121 38700 70 14 90 9 12 121 48600 70 17 95 11 14 121 29600 90 10 105 7 9 126 39800 90 14 110 9 11 126 49800 90 18 115 11 14 126 29300 105 1...

Страница 31: ...ased upon the lower voltage of dual voltage rated units Heat Rejection Capacity Air Temp Entering Fluid Cooler DB Air ΔT Water Flow Rate Water Temp Entering Fluid Cooler Water ΔT through Fluid Cooler Approach Temp Fan Power BTUH F F GPM F F F Watts 44100 70 9 15 85 6 9 187 59400 70 13 90 8 12 187 74500 70 16 95 10 15 186 44500 90 10 105 6 9 184 59300 90 13 110 8 12 184 74000 90 17 115 10 15 183 43...

Страница 32: ...iron or galvanized piping or components in the system Should periodic cleaning be necessary use standard cleaning procedures which are compatible with both the heat exchanger material and copper water lines Generally the more water flowing through the unit the less chance for scaling However flow rates over 3 gpm per ton 3 9 l m per kW can produce water or debris velocities that can erode the heat...

Страница 33: ...6 9 1 5 81 38 57 134 6 2 77 12 10 4 61 70 58 136 4 2 67 11 12 2 58 40 59 138 2 2 58 10 14 0 55 30 60 140 0 2 49 9 15 8 52 38 61 141 8 2 40 8 17 6 49 64 62 143 6 2 32 7 19 4 47 05 63 145 4 2 23 6 21 2 44 61 64 147 2 2 16 5 23 0 42 32 65 149 0 2 08 4 24 8 40 15 66 150 8 2 01 3 26 6 38 11 67 152 6 1 94 2 28 4 36 18 68 154 4 1 88 1 30 2 34 37 69 156 2 1 81 0 32 0 32 65 70 158 0 1 75 1 33 8 31 03 71 15...

Страница 34: ...Tranquility Fluid Cooler 60 Hz Rev Feb ru ar y 22 2022 Geothermal Heating and Cooling 34 Notes ...

Страница 35: ...Tranquility Fluid Cooler 60 Hz Rev Februar y 22 2022 climatemaster com 35 Notes ...

Страница 36: ...not be as described herein Please contact ClimateMaster s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products 7300 S W 44th Street ...

Отзывы: