HK 200M

Connection to the heat pump

Connection when operating without a 
heat pump

Connection of hot and cold water

All outdoor pipes must be thermally insulated with a 
pipe lining with at least 20mm thickness.
HK 200M is not equipped with cut-off valves, which 
must be installed outside the indoor module to make 
future maintenance easier.

When connecting to the installation where all heaters/

floor heating pipes have been equipped with thermo

-

stat valves, in order to assure appropriate flow, install 

a discharge valve or a buffer in the parallel layout, or 
remove several thermostats.

Connect the input pipe from the heat pump (XL8) to 
output pipe XL9 of the heat pump.

The  installation  of  the  mixing  valve  is  necessary 

if factory settings are changed in a way where the 

temperature  can  exceed  60°C.  When  changing  the 

factory settings, follow the national regulations in this 
respect. The setting is entered in  menu 5.1.1.

Connection of the heating system

The system can be extended by additional circuits ac

-

cording to the capacity of the applied control module: 

SMO 20 or SMO 40. 

Additional accessories, capacity and connection 

method have been specified in the manual for SMO 

20 and SMO 40, in chapters   Accessories and Elec

-

trical connections. 

Cooling system connection

Cooling  is  controlled  by  sensor  BT64  and  isolation 

valve QN12. If cooling is needed, the isolation valve 

changes the direction, and opens from the cooling 
circuit side. 

Optional connections 

Chapter 4 | 

Pipe connections

P

P

P

P

P

HK 200 M

Connection options

Содержание HK 200M

Страница 1: ...15 02 2017 25957 HK 200M Installation manual Indoor unit cooperating with air heat pumps HK 200M ...

Страница 2: ...O 40 In order to temporarily increase hot water volume first turn the control knob to mark menu 2 icon present ing water drop and press the OK button twice More information to be found in section Setting hot water output If there are any distortions to the heat comfort before contacting the installation technician you can per form some activities yourself Appropriate instructions can be found in s...

Страница 3: ..._____ 15 5 Electrical connections ______ 16 General information _____________________ 16 Connections ___________________________ 17 Settings ______________________________ 24 6 Start up and regulation _____ 25 Preparations___________________________ 25 Filling and venting ______________________ 25 Start up and acceptance _________________ 26 7 Control __________________ 27 Display ________________...

Страница 4: ... children Rights to introduce structural changes reserved NIBE BIAWAR 2016 This manual contains installation and maintenance proce dures for specialists The serial number is located at the top of HK 200M IMPORTANT This symbol informs about the risk to the device or a person CAUTION This symbol points to important information to be not ed when operating the device ADVICE This symbol shall mean tips...

Страница 5: ...er supply Communication connection Circuit fuses Fuses internal module Building fuses temperature sensor outdoor Room sensor Energy meter Emergency switch Switch differential Thermostat emergency mode setting Miscellaneous Connected to Installation acceptance The heating system must be accepted before start up Acceptance must be done by a person with appropriate qualifications Complete the card in...

Страница 6: ... waterproof base that would keep the weight of the indoor unit The regulated legs of the heat pump allow for levelling and stable setting of the device Because HK 200M is equipped with condensate drain the installation site of the indoor module must be furnished with a floor drain with a dis charge to the sewer system 1 Remove screws at the bottom edge of the front cover 2 Tilt the cover at the bo...

Страница 7: ...7 HK 200M 3 Indoor module structure Chapter 3 Indoor module structure HK 200M EB2 XL11 QN12 QN10 GP12 CM1 EB1 XL3 XL8 XL4 XL1 EB15 BT71 BT6 BT64 BT63 BT7 BT25 BT3 ...

Страница 8: ...ating QN12 Isolation valve cooling heating GP12 Circulation pump Sensors BT3 Temperature sensor heating medium re turn BT6 Temperature sensor hot water loading BT7 Temperature sensor top of the hot water heater BT25 Temperature sensor heating medium supply BT63 Temperature sensor heating medium supply downstream the submersible heat er BT64 Temperature sensor cooling medium supply BT71 Temperature...

Страница 9: ... bar 5 mvp shall mean maximum permissible height difference of 5 m If the standard initial pressure in the diaphragm ex pansion vessel is too low it can be raised by filling the vessel through the valve installed Any change to the initial pressure affects the dia phragm expansion vessel s capacity to support the increase in water volume IMPORTANT All places in the heating system located high must ...

Страница 10: ...erating within the range of low temperatures up to 20 C The connection of the outdoor unit and indoor unit HK 200M with a system of pipes filled with a cooling medium secures the connection against freezing in the event of any power outages The control of sys tem operation is the function of SMO 20 or SMO 40 module Installation diagram Chapter 4 Pipe connections Symbol Meaning Vent Cut off valve W...

Страница 11: ...ated legs Pipes must be led in such a way that they are not adjacent to the bedroom or living room Remember to leave about 800 mm free space at the front and 500 mm over the device to provide for future maintenance 1 Connect HK 200M module to the heating system cold and hot water pipelines 2 Use hydraulic connections to connect the outdoor and indoor unit 3 Connect the current meter outdoor temper...

Страница 12: ...y Ø22 mm XL2 Connection Heating medium return Ø22 mm XL3 Connection hot water Ø22 mm XL4 Connection cold water Ø22 mm XL5 Connection circulation Ø15 mm XL8 Connection supply of the heating medi um from the external unit Ø22 mm XL9 Connection discharge of the heating me dium to the external unit Ø22 mm XL10 Connection cooling Ø22 mm XL11 Connection safety group Ø22 mm manometer Other information PF...

Страница 13: ... entire length from the safety valve and must be secured against freezing When connecting to the installation where all heaters have been equipped with thermostat valves install a discharge valve or remove sever al thermostats to assure appropriate flow IMPORTANT The term heating system as used in this installation and operation manual shall mean the heating or cool ing system supplied with a hot ...

Страница 14: ...door pipes must be thermally insulated with a pipe lining with at least 20mm thickness Install cut off and drain valves to allow for emp tying the outdoor unit in case of long power out ages The supplied flexible hoses act as vibration ab sorbers Flexible hoses must be installed to form elbows that would attenuate vibrations Connection between the outdoor and in door unit Chapter 4 Pipe connection...

Страница 15: ...e heat pump The installation of the mixing valve is necessary if factory settings are changed in a way where the temperature can exceed 60 C When changing the factory settings follow the national regulations in this respect The setting is entered in menu 5 1 1 Connection of the heating system The system can be extended by additional circuits ac cording to the capacity of the applied control module...

Страница 16: ... module from the back wall towards the front wall IMPORTANT As long as the heating circuits have not been filled with the heating medium and if the central heating system has not been vented the switch SF1 in SMO cannot be set in positions I or Otherwise the tempera ture limiter thermostat and flow through heater can be damaged X1 Terminal block for low voltage X2 Terminal block for high voltage X...

Страница 17: ...MPORTANT In order to prevent interferences do not lay unshielded communication and or signal cables to external con tacts at the distances lower than 20 cm from high volt age cables Power supply connection Temperature limiter Temperature limiter F3 cuts off the power supply of the electrical heating module if the temperature in creases to the range of approximately 87 C and can be reset manually F...

Страница 18: ... X2 L HK 200M HK 200M SMO 20 SMO 40 SMO 20 40 N PE SMO X2 PE L N HK 200M SMO 20 SMO 40 9 8 7 6 5 4 AA2 X4 X2 GP12 LEK L N 1 1 0 2 3 4 PE AA2 X4 SMO 20 40 L N PE HK 200M X2 Chapter 5 Electrical connections SMO 20 SMO 40 Connect the control signal GP12 for SMO 20 to clamps X2 1 PWM and X2 2 GND while for SMO 40 to clamps X4 8 and X4 7 according to the draw ing 2 1 4 3 SMO Externt HK 200M SMO 20 SMO ...

Страница 19: ...r SMO 20 to clamps X2 4 and X2 6 while for SMO 40 to clamps X6 15 and X6 16 Use a two wire cable with the cross sec tion of at least 0 5 mm 5 6 7 2 1 4 3 HK 200M SMO 20 X2 X1 BT6 LEK L N 1 1 0 2 3 4 PE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2 5 6 7 2 1 8 9 13 12 4 3 11 10 19 20 21 14 18 16 17 15 SMO 20 HK 200M X1 HK 200M SMO 40 X1 BT6 6 7 8 9 10 11 12 13 AA3 X6 SMO 40 L N 1 1 0 2 3...

Страница 20: ... 200M X1 SMO 20 SMO 40 Temperature sensor on the supply pipeline at the heating module upstream the isolation valve QN10 Temperature sensor on the pipeline downstream the heating module BT63 must be connected in SMO 20 to clamps X2 9 and X2 10 while in SMO 40 to AUX clamps e g X6 13 and X6 14 and then turn on sensor power supply see SMO40 installation man ual Use a two wire cable with the cross se...

Страница 21: ... while in SMO 40 to clamps X6 15 and X6 16 at the input card AA3 Turning the cooling function on in the heat pump see SMO installation manual 13 14 15 10 12 11 HK 200M SMO 20 SMO 20 X1 X2 BT64 LEK L N 1 1 0 2 3 4 PE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X2 5 6 7 2 1 8 9 13 12 4 3 11 10 19 20 21 14 18 16 17 15 SMO 20 AUX1 AUX2 AUX3 AUX4 HK 200M X1 HK 200M SMO 40 X1 BT64 AA3 X6 L N 1...

Страница 22: ...tep controlled heating module are entered in menu 4 9 3 and menu 5 1 12 All auxiliary heaters can be blocked by connecting the potential free relay function to clamp X2 of the program controlled input see SMO manual Chap ter Electrical connections section Optional Connec tions Flow through heating element SMO 6 1 0 PE HK 200M SMO 20 SMO 40 AA7 X2 X1 L N 1 1 0 2 3 4 PE 1 2 3 4 LEK 1 2 3 4 X1 1 1 N ...

Страница 23: ...MO 20 at out puts AUX X4 15 and X4 16 while for SMO 40 at out puts AUX X7 C and X7 NO Isolation valve QN10 Isolation valve QN12 1 2 3 4 5 6 SMO SMO 20 SMO 40 AA2 X4 L N 1 1 0 2 3 4 PE 1 2 3 4 LEK 1 2 3 4 AA2 X4 SMO 20 40 HK 200M X2 QN10 Brown Black N HK 200M X2 HK 200M SMO 20 X2 QN12 AA3 X4 Brown Black N 15 6 1 17 LEK L N 1 1 0 2 3 4 PE AA2 X4 SMO 20 X1 1 2 3 0 PE X1 1 1 N L 0 4 3 2 PE HK 200M X2 ...

Страница 24: ...Load sensor has not been connected Constant temperature in the supply pipeline more information to be found in the Chapter w Emergency Mode Thermostat In the emergency mode the supply temperature is set using a thermostat T1 It must be set according to the demand of the circuits in operation The available regulation range is between 6 and 67 C Remember that for floor heating the settings must be m...

Страница 25: ...low in all circuits 3 Open the valve for filling the heating installation and fill it with the heating medium 4 Close the vent when the heating medium flows out of it continuously without air bubbles 5 Control the manometer showing pressure in crease Fill the system until the pressure of 2 bar and then close the filling valve 6 Start the circulation pump of the heating system every now and then wh...

Страница 26: ...lation of the heat pump Enter menu 5 2 2 System settings and turn the heat pump off IMPORTANT Select auto or manual operating mode when the in door module is to be used again with the heat pump Pump speed The circulation pump in HK 200M is controlled by fre quency and is automatically regulated via control and based on the heating demand Available pressure circulation pump Pressure kPa Flow l s La...

Страница 27: ... found in the Help menu or in the operating manual Advanced settings These settings are not available to the end user This menu will be visible if the Back button is pressed in the start menu for 7 seconds Setting and programming hot water production More information to be found in the Help menu or in the operating manual Room climate Menu 1 Information Menu 3 My system Menu 4 Service Menu 5 DHW M...

Страница 28: ...on In order to make maintenance of the heating system easier the system must first be emptied using the fill ing valve 1 Connect the hose to the bottom valve for heating medium filling 2 Open the valve to empty the heating system Emergency mode is switched on by appropriately set ting the switch SF1 in the mode This means that Status control is on in yellow The display is not on and the controller...

Страница 29: ...played Detailed information regarding distorted heat comfort can be found in the manual for SMO 20 or SMO 40 in the chapter with the same title Accessories that can be used depend on the applied Control Module SMO 20 or SMO 40 The list of all possible accessories can be found in the relevant manual of the Control Module applied 10 Accessories Chapter 9 Chapter 10 Distorted heat comfort Accessories...

Страница 30: ...30 HK 200M 11 Technical data Dimensions and layout of con nections Chapter 11 Technical data 20 40 1600 95 300 155 45 95 90 120 85 65 55 600 610 315 70 65 ...

Страница 31: ...he heating system yes Safety valve heating system yes Diaphragm expansion vessel l 10 Auxiliary preheater kW 9 Rated voltage V 3x400 Anticorrosive protection Enamel titanium anode Maximum DHW capacity 230 l 40 C Kit energy class F2040 HK 200M SMO 12 kW Energy class acc to ErP at supply temp 55 C A Performance class Load profile DHW A XL Chapter 11 Technical data Technical data ...

Страница 32: ...agram of electrical connec tions 3 x 400 V Chapter 11 Technical data 5G2 5mm 3G1 5mm 2 2 K1 K2 3x1 5kW 3x1 5kW Immersion heater F2 10A X2 L N PE L N PE SMO F3 98 8 C X3 L N N L PE K3 Supply Voltage 400V 3N AC 50 Hz ...

Страница 33: ...L PE TITANIUM ANODE X3 2 1 2 1 K2 EMERGENCY L K1 N X2 PE Brown Black Black White N Brown Black N T1 5 80 C M 1 GP12 K2 K1 M 1 QN12 M 1 QN10 BT6 X1 BT6 BT7 BT7 BT63 BT63 BT25 BT25 BT71 BT71 BT6 BT7 BT63 BT25 BT71 PWM GND K3 K3 BT64 BT64 BT64 AA8 ...

Страница 34: ...34 HK 200M Notes ...