Replacement Parts
Returning a Defective Unit
Network Controller 6 Mounting and Wiring Guide
Part Number 11843 Rev 2.1
Updated: January 16, 2012
25
b.
Remove the installed accessory modules, starting with the end module. Modules may be secured
by screws in mounting tabs or clipped to a DIN rail, or fastened by some combination. See
on page 6 for details on removal from (and mounting onto) DIN rail.
c.
Remove any screws fastening the T-600, and remove it (see
).
Step 6
Remove the cover from the old T-600 (see
“Removing and Replacing the Cover,”
page 6).
Note the position of installed option boards, if any. You must transfer them to the replacement T-600.
Step 7
Remove the option boards from the old T-600 controller and install them into the replacement T-600,
if applicable. See
page 9, for more details.
Step 8
Check the RS-485 biasing jumpers on the existing unit, and duplicate on the replacement unit (see
Step 9
Mount the replacement T-600 as it was previously, using the same DIN rail location and/or screws.
Step 10
Reconnect/remount any removed accessory modules, being careful to replace in the same order, using
the same DIN rail location and/or screws. Secure all accessory modules as done previously.
Step 11
Reconnect earth ground wires to the controller’s grounding lug and any installed accessory modules.
Step 12
Reconnect any Ethernet, serial, modem, and I/O connectors to the controller and any installed
accessory modules.
Step 13
If using IO modules, and any of your I/O points have voltage, turn the devices back on, or reconnect
power to them.
Step 14
Restore power to the T-600. It should boot up as a new unit (see
page 20).
Step 15
Using the NiagaraAX platform tools, re-commission the T-600, and install the saved station database.
For more details, see the
JACE NiagaraAX Install and Startup Guide
.
Returning a Defective Unit
For proper credit on an in-warranty unit, ship the defective unit per the vendor’s return material procedure.
Note
If the defective unit is under warranty, please follow return instructions provided in this section.
If the unit is
out of warranty
, please discard it, observing all recycling regulations (see
of Electrical and Electronic Equipment),”
•
Do not return an out-of-warranty T-600 controller.
Prior to returning the unit, contact your vendor to obtain a return materials authorization (RMA) number and
other instructions.
Please provide:
•
Product model
•
Serial number
•
Nature of defect
•
PO number to secure the RMA