Network Controller 6 Mounting and Wiring Guide
Updated: January 16, 2012
About Expansion Options
About Accessory Modules
10
About Accessory Modules
The T-600 controller has a 20-pin, right-angle, Euro-DIN connector that accepts custom-built accessory
modules. The connector provides power and signal lines to any connected modules, and is located on the end of
the T-600 opposite to the option cards.
Warning
•
Power to the controller must be OFF when inserting or unplugging accessory modules.
Wait for all LED activity to stop (all LEDs to be off).
•
Also, do not connect live voltages to the inputs or outputs of an I/O module (T-IO-16 or T-IO-34)
while it is in an “un-powered state” before plugging the module into a T-600.
Otherwise,
damage to the I/O module and/or the controller may result
!
Each accessory module has a DIN-mount base, and typically provides two (2) 20-pin connectors that allow you
to “chain” multiple accessories (see
lists currently available accessory modules.
Table 2
T-600 accessory modules.
Model
Description
Notes
DIN-mountable, 24V isolated power
module, used to power T-600 from a
dedicated, external, Class-2, 24Vac
transformer
or
a 24Vdc power supply.
•
Only one NPB-PWR per T-600 controller.
•
Do not install if using
or
•
Wiring is covered in
this document
, see
DIN-mountable, Universal 90–263
Vac input, 15Vdc output, 30W power
supply to power T-600.
•
Only one NPB-PWR-UN per T-600 controller.
•
Do not install if using
or
•
Wiring is covered in
this document
, see
T-IO-16
DIN-mountable, 16 points I/O module,
used to provide I/O points as noted.
Provides the following I/O points:
• 8 - Universal Inputs (UIs).
• 4 - Digital Outputs (DOs), SPST-relay type.
• 4 - Analog Outputs, 0–10Vdc type.
Up to four (maximum) T-IO-16 accessory modules are supported.
Wiring is covered in a
separate
document, see the
T-IO-16 Installation and Configuration Guide
.
T-IO-34
DIN-mountable, combined 34 points
I/O with 24V isolated power module,
used to provide I/O points as well as
power T-600 from a dedicated,
external, Class-2, 24Vac transformer
or
a 24Vdc power supply.
Only one T-IO-34 per T-600. Provides the following I/O points:
• 16 - Universal Inputs (UIs).
• 10 - Digital Outputs (DOs), SPST-relay type.
• 8 - Analog Outputs, 0–10Vdc type.
Up to 2 additional T-IO-16 modules can be used. Do not power the
T-IO-34 if using
.
Wiring is covered in a
separate
document, see the
T-IO-34 Installation and Configuration Guide
.