Figure 2.

 cRIO-9067 Front Panel

7

8

2

5

1

6

3

4

1. LEDs
2. USB Device Port
3. RS-232 Serial Port
4. RJ-45 Ethernet Port 2

5. RJ-45 Ethernet Port 1
6. USB Host Port
7. Power Connector
8. RESET Button

Connecting the cRIO-9067 to Ground

You must connect the cRIO-9067 grounding terminal to the grounding electrode system of the
facility.

What to Use

Ring lug

Wire, 2.1 mm

2

 (14 AWG) or larger

Screwdriver, Phillips #2

What to Do

Complete the following steps to ground the cRIO-9067.
1.

Attach the ring lug to the wire.

2.

Remove the grounding screw from the grounding terminal on the cRIO-9067.

3.

Attach the ring lug to the grounding terminal.

4.

Tighten the grounding screw to 0.5 N · m (4.4 lb · in.) of torque.

5.

Attach the other end of the wire to the grounding electrode system of your facility using a
method that is appropriate for your application.

Caution

 

If you use shielded cabling to connect to a C Series module with a plastic

connector, you must attach the cable shield to the chassis grounding terminal using
2.1 mm

2

 (14 AWG) or larger wire. Attach a ring lug to the wire and attach the wire

to the chassis grounding terminal. Solder the other end of the wire to the cable
shield. Use shorter wire for better EMC performance.

For more information about ground connections, visit 

ni.com/info

 and enter the Info Code

emcground

.

6

  | 

ni.com

  | 

NI cRIO-9067 Getting Started Guide

Содержание cRIO-9067

Страница 1: ...afety protection built into the product if the product is damaged in any way If the product is damaged return it to NI for repair Safety Guidelines for Hazardous Locations The cRIO 9067 is suitable fo...

Страница 2: ...own to be nonhazardous Table 1 Hazardous Location Retention Accessories Port Required Accessory Part Number USB Device Port NI Locking USB Cable 157788 01 USB Host Port NI Industrial USB Extender Cabl...

Страница 3: ...authority to operate it under your local regulatory rules Caution To ensure the specified EMC performance operate this product only with shielded cables and accessories Special Conditions for Marine A...

Страница 4: ...connectors Note Do not install a device if it appears damaged in any way 3 Unpack any other items and documentation from the kit Store the device in the antistatic package when the device is not in u...

Страница 5: ...n the C Series module 3 Align the C Series module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector...

Страница 6: ...3 Attach the ring lug to the grounding terminal 4 Tighten the grounding screw to 0 5 N m 4 4 lb in of torque 5 Attach the other end of the wire to the grounding electrode system of your facility usin...

Страница 7: ...0 10 in flathead Power supply 9 V to 30 V 25 W maximum NI recommends the power supply listed in the following table for the cRIO 9067 Table 3 NI Power Supplies Power Supply Part Number NI PS 15 Indust...

Страница 8: ...eps to connect the cRIO 9067 to the host computer using the USB device port 1 Power on the host computer 2 Connect the cRIO 9067 to the host computer using the USB A to B cable Caution NI requires the...

Страница 9: ...ring prompts you to do so 2 Enter a unique name for your system in the Hostname field 3 Click the Security Configuration icon 4 Click Login 5 In the Login dialog box enter the username admin and leave...

Страница 10: ...rmat of 172 22 11 x 2 In MAX expand your system under Remote Systems 3 Select the Network Settings tab to configure the IP and other network settings 4 Optional Use the RJ 45 Ethernet port 1 to reconn...

Страница 11: ...ul and appropriate for your application skip to Step 6 4 In MAX expand your system under Remote Systems 5 Select the Network Settings tab to configure the IP and other network settings 6 Reboot the cR...

Страница 12: ...are has been improperly installed on the cRIO 9067 An error can occur when an attempt to upgrade the software is interrupted Reinstall software on the cRIO 9067 Refer to the Measurement Automation Exp...

Страница 13: ...actriodevguide Software Support ni com info swsupport Support ni com support SOFTWARE CompactRIO Sample Projects LabVIEW Create Project HARDWARE NI cRIO 9067 Specifications ni com manuals NI cRIO 9067...

Страница 14: ...nch office websites which provide up to date contact information support phone numbers email addresses and current events Refer to the NI Trademarks and Logo Guidelines at ni com trademarks for inform...

Отзывы: