background image

1.2

TRACE

MATE-277V

Product Overview

Temperature Range

Range:

-50°C to 500°C, -58°F to 932°F

Hysteresis:

±2°C, ±3.2°F

Absolute Accuracy:

±2.5°C, ±4.5°F

Repeatability:

±1°C, ±1.8°F

RTD:

100 ohm platinum, 3-wire 20 ohms
maximum lead resistance

Heater Switching

Installaton/Overvolatge CAT. III; Pollution Degree 2
Configuration

TM-1SIH1-E5-RTD-277V Single-pole
TM-1DIH2-E5-RTD-277V Dual-pole
Dual SCR, one per phase

Ratings:

TM-1SIH1-E5-RTD-277V 277Vac @ 30
amps
TM-1DIH2-E5-RTD-277V 277VAC
@30amps
250 amp 1/2 cycle inrush

Line Frequency

50 or 60Hz

Control Power

Installaton/Overvolatge CAT. III; Pollution Degree 2
Power Requirements

Control power from heater voltage
TM-1SIH1-xx 277VAC, 10VA
TM-1DIH2-xx 277VAC, 10VA

Protection

Control power from heater voltage
protected by non-replaceable 2A, time
lag, 350 VAC fuse
MOV transient protection and RC
snubber

User Interface

Heater Setpoint

12 position dip switch

Reset/Heater Test

dip switch

Panel Indicators

Power on
Heater on
Low temperature alarm
High temperature alarm
Current fail alarm
Ground fault trip alarm
RTD fail alarm

Environment

Approvals:

CSA NRTL/C and FM
Class I, Div.2, Groups A,B,C,D
Class I, Zone 2, Groups IIC

Operating Range:

TM-1SIH1-xx: -40°C to +50°C
TM-1DIH2-xx: -40°C to +50°C
Heater current derated

Conformal Coating:

Boards conformal coated for hostile
environments. Altitude: 0-2000m

User-Definable Options

Heater Setpoint:
Low Temperature Alarm Setpoint:
High Temperature Alarm Setpoint:

0°C-511°C, 1°C steps
0°F-511°F, 1°F steps

Temperature Units:

0°C or °F

Current Fail Alarm Setpoint:

0.0A-30.0A, 1 A steps

Ground Fault Trip Alarm Setpoint:

0mA-511mA, 1 mA steps

Enclosure

Type:

E5: Nema-4X steel, painted black

Size:

TM-1SIH1-xx: 8”Hx6”W x4”D
TM-1DIH2-xx: 10”Hx8”W x4”D

Features:

Quick release latches to open door
One 3/4” conduit knockout for power
and two 1/2” conduit knocks for RTD
and signal wiring.

Alarms

Installaton/Overvolatge CAT. II; Pollution Degree 2
Low Temperature:

Actual temperature < low temperature

alarm setpoint

High Temperature:

Actual temperature > high temperature

alarm setpoint

Current Fail:

Heater current < current fail alarm
setpoint

Ground Fault Trip:

Ground fault current > Ground fault trip
alarm setpoint

RTD Fail:

RTD Open, RTD Short

Hardware:

No incoming voltage

TraceCheck:

Current Fail Alarm

Configurationt:

NC/NO Contacts

Alarm Output Rating:

Form C dry contact: 30Vdc/0.1A
LED Indicator: 6VDC/50mA

Alarm Function

Temperature:

Low Temperature Alarm
High Temperature Alarm

Current:

Current Fail Alarm

Ground Fault

Ground Fault Trip

Hardware

RTD Open, RTD Short

Specifications

H e ater C u rren t R ating

1 an d 2-P ole Sw itch in g

0

5

1 0

1 5

2 0

2 5

3 0

3 5

-1 0

0

1 0

2 0

3 0

4 0

5 0

Am bien t A ir T em p (°C )

H

eat

er

C

u

rr

e

n

t

(A

m

p

s)

1-Pole

2-Po

le

Содержание Tracemate-277V

Страница 1: ...TRACEMATE 277V OPERATOR S MANUAL ELECTRONIC THERMOSTAT ISO 9001 Registered ...

Страница 2: ...and Cabling 2 3 Power Wiring 2 3 Heater Wiring 2 3 Ground Connection 2 3 RTD Sensor Wiring 2 3 Alarm Wiring 2 4 3 Applications 3 1 Mechanical Thermostat Replacement 3 1 Alarm Annunciator 3 1 Switching Requirements 3 1 4 Operation 4 1 Alarms 4 1 Status Indicators 4 1 Alarm Reset 4 1 Heater Setpoint and Alarm Setpoints 4 1 5 Testing 5 1 Troubleshooting System Integrity 5 1 Calibration 5 1 Ground Fau...

Страница 3: ...ng requirements of a heat trace control system into a general purpose control the TraceMate 277V makes it possible to significantly upgrade systems at low installed cost In addition it is very flexible in its application to adapt to specific user requirements Conventions The following conventions are used in this manual Features and Benefits Re quirem ents TraceM ate 27 7V F ea ture s Te m p era t...

Страница 4: ...nt derated Conformal Coating Boards conformal coated for hostile environments Altitude 0 2000m User Definable Options Heater Setpoint Low Temperature Alarm Setpoint High Temperature Alarm Setpoint 0 C 511 C 1 C steps 0 F 511 F 1 F steps Temperature Units 0 C or F Current Fail Alarm Setpoint 0 0A 30 0A 1 A steps Ground Fault Trip Alarm Setpoint 0mA 511mA 1 mA steps Enclosure Type E5 Nema 4X steel p...

Страница 5: ...arm setpoint in mA AMP Setpoint Number generated by S1 9 is divided by 10 and interpreted as current fail alarm setpoint in A SP Setpoint Number generated by S1 9 is interpreted as heater setpoint in C or F NONE Setpoint Number generated by S1 9 has no effects on any setpoints Warning The ground fault trip function is intended for equipment protection only and should not be used in place of ground...

Страница 6: ...2 2 TRACEMATE 277V Chapter 2 Installation Figure 2 1 TraceMate 277V Controls and Indicators Figure 2 2 Typical Wiring Diagram ...

Страница 7: ... Temperature C 6 30 50 8 30 40 10 24 50 12 16 50 The supply voltage must be 277VAC for TM 1SIH1 E5 RTD 277V Single pole TM 1DIH2 E5 RTD 277V Dual pole and rated voltage range of the heat trace cable Wiring methods must conform to Class 1 Division II or Class 1 Zone II requirements Heater Wiring Connect heating cable wiring to terminals 3 and 4 See Figure 2 2 If the heating cable has a braid it sho...

Страница 8: ...m Wiring TraceMate 277V has a form c dry alarm and an active alarm output for driving an LED alarm indicator The alarm LED output is configured to turn on the alarm indicator when there is no alarm Refer to Figure 2 2 for alarm output terminals The form c dry alarm contact is rated 0 1A 30Vdc The alarm LED output is rated 6Vdc 50mA It can drive a 6Vdc LED indicator These alarm contact and output a...

Страница 9: ...ent of a problem Alarm Annunciator If an alarm annunciator or programmable controller is available terminal 10 11 12 can be used as a low cost digital interface These terminals are form c dry con tacts A separate voltage source must be connected across these terminals as shown in Figure 3 2 for the annuncia tor to sense the alarm logic Switching Requirements Two different TraceMate 277V models are...

Страница 10: ...e shut off after a ground fault it is very important that the alarm outputs be used so corrective action can be taken quicklyenough to prevent a process shutdown due to the loss of heat to a pipe Ground fault detection only works with resistance or solidly grounded systems If the system is ungrounded it must be grounded or an artificial ground must be created by means of a zip zag transformer Once...

Страница 11: ...ber generated by S1 9 is interpreted as the high temperature alarm setpoint in C or F The factory default value is 100 C Ground Fault Trip Alarm Setpoint If the jumper on JP1 is at GF position the Setpoint Number generated by S1 9 is interpreted as the ground fault trip alarm setpoint in mA The factory default value is 30 mA Current Fail Alarm Setpoint If the jumper on JP1 is at AMP position the S...

Страница 12: ...can be verified by adjusting the heater setpoint dip switch 2 C above and below a known temperature on the RTD input to see if the heater turns on and off For example if the RTD input temperature is 25 C setting the heater setpoint to 27 C will force the heater on and conversely a 23 C setpoint will force the heater off By substituting a known resistor value for the RTD sensor and looking up the e...

Страница 13: ...round fault sensor as a ground fault Size the resistor according to the table to ensure sufficient ground fault current of 30mA 25 Heater Voltage 110 240 277 AC Volts Resistance 2700 6200 6800 Ohms Wattage 5 10 15 Watts Voltage Rating 250 500 500 DC Volts 4 Apply power The ground fault indicator should come on after a short delay It should not be possible to turn on the heater even if the actual t...

Страница 14: ...OVIDED FOR IN WRITING IN THIS WAR RANTY EACH CONTROL IS PROVIDED WITHOUT ANY WARRANTY OF ANY KIND EITHER EXPRESSED OR IMPLIED IN PARTICULAR WITH OUT LIMITING THE GENERALITY OF THE FOREGOING THE FOLLOW ING IMPLIED WARRANTIES AND CONDITIONS ARE EXPRESSLY DIS CLAIMED a ANY IMPLIED WARRANTY OR CONDITION THAT THE CON TROL WILL MEET YOUR REQUIREMENTS b ANY IMPLIED WARRANTY OR CONDITION THAT THE OP ERATI...

Страница 15: ...TRACEMATE 277V ELECTRONIC THERMOSTAT P N 1501 0013_1 TMII 277V 02 09 Printed in Canada Nextron Corporation 6120 11th Street S E Calgary Alberta T2H 2L7 Tel 403 735 9555 Fax 403 735 9559 ...

Отзывы: