2.3

Chapter 2 Installation

Mounting the Controller

Mount the control panel with Unistrut brackets using 3/
8” bolts. The Unistrut (or equivalent) mounting allows
air circulation to cool the heat-sink. This is important to
ensure proper operation of the TraceMate-277V.
Mounting dimensions are shown in Figure 2.5.

Wire Sizing

Conduit and Cabling

TraceMate-277V comes with one 3/4” and 1/2” conduit
knockouts located on the bottom of the enclosure.
Conduit hubs should be NEMA-4X rated, such as T&B
H050-0.5 and H075-0.75 or Myers equivalent, to main-
tain a watertight seal. Unused knockouts should be sealed
using NEMA-4X rated seals.

Power Wiring

The power input terminals supply power to both the heat
trace and controller. Size power input wires appropriately
to the breaker size and maximum ambient operating
temperatures. Maximum breaker size is 30A. Connect
power wires to input terminals 1 and 2. See Figure 2.2.
The breaker should be placed as close as possible to the
TraceMate-277V.

The RTD probe is delicate and should not
be bent or used as a tool to puncture
insulation.

Wiring methods should comply with Canadian
Electrical or National Electrical Code and
local codes. Power and signal wires should not
be run in the same conduit system. Wiring
should be rated at least 90 °C, 300 V Min.

Wire Size (AWG)

Current Load (A)

Max. Ambient

Temperature (°C)

6

30

50

8

30

40

10

24

50

12

16

50

The supply voltage must be 277VAC for TM-
1SIH1-E5-RTD-277V ( Single-pole ), TM-
1DIH2-E5-RTD-277V ( Dual-pole ) and rated
voltage range of the heat trace cable.

Wiring methods must conform to Class 1,
Division II or Class 1, Zone II requirements.

Heater Wiring

Connect heating cable wiring to terminals 3 and 4. See
Figure 2.2. If the heating cable has a braid, it should be
terminated to the ground stud using a ring terminal
suitable for #10 stud.

Figure 2.3 Ground Connection

Ground Connection

Connect the controller grounding stud directly to a ground
bus using the shortest, practical path. Use a tinned copper,
braided bonding cable such as Belden 8660. As a guide-
line, the ground cables should be minimum 96 strands,
number 34 AWG each.
To install the ground connection, remove the outside nut,
washer and #8 ring lug provided on the ground stud.
Crimp the ground cable onto the ring lug and re-assemble
onto the ground stud using the washer and nut.

Figure 2.4 RTD Mounting

RTD Sensor Wiring

RTD sensors should be 3-wire, 100 ohm, platinum to DIN
standard 43760. Mount the RTD element on the pipe,
away from the heat trace and 30° to 45° from the bottom
of the pipe. The total circuit resistance per conductor
from the RTD to the control panel must be less than 10
ohm. Exceeding this resistance will result in a non-linear
temperature measurement. Beldon cable 8770 or
equivalent allows RTDs to be placed up to 1,000 feet
from the control panel. Complete all RTD wiring accord-
ing to Figure 2.2 Typical Wiring Diagram.

Содержание Tracemate-277V

Страница 1: ...TRACEMATE 277V OPERATOR S MANUAL ELECTRONIC THERMOSTAT ISO 9001 Registered ...

Страница 2: ...and Cabling 2 3 Power Wiring 2 3 Heater Wiring 2 3 Ground Connection 2 3 RTD Sensor Wiring 2 3 Alarm Wiring 2 4 3 Applications 3 1 Mechanical Thermostat Replacement 3 1 Alarm Annunciator 3 1 Switching Requirements 3 1 4 Operation 4 1 Alarms 4 1 Status Indicators 4 1 Alarm Reset 4 1 Heater Setpoint and Alarm Setpoints 4 1 5 Testing 5 1 Troubleshooting System Integrity 5 1 Calibration 5 1 Ground Fau...

Страница 3: ...ng requirements of a heat trace control system into a general purpose control the TraceMate 277V makes it possible to significantly upgrade systems at low installed cost In addition it is very flexible in its application to adapt to specific user requirements Conventions The following conventions are used in this manual Features and Benefits Re quirem ents TraceM ate 27 7V F ea ture s Te m p era t...

Страница 4: ...nt derated Conformal Coating Boards conformal coated for hostile environments Altitude 0 2000m User Definable Options Heater Setpoint Low Temperature Alarm Setpoint High Temperature Alarm Setpoint 0 C 511 C 1 C steps 0 F 511 F 1 F steps Temperature Units 0 C or F Current Fail Alarm Setpoint 0 0A 30 0A 1 A steps Ground Fault Trip Alarm Setpoint 0mA 511mA 1 mA steps Enclosure Type E5 Nema 4X steel p...

Страница 5: ...arm setpoint in mA AMP Setpoint Number generated by S1 9 is divided by 10 and interpreted as current fail alarm setpoint in A SP Setpoint Number generated by S1 9 is interpreted as heater setpoint in C or F NONE Setpoint Number generated by S1 9 has no effects on any setpoints Warning The ground fault trip function is intended for equipment protection only and should not be used in place of ground...

Страница 6: ...2 2 TRACEMATE 277V Chapter 2 Installation Figure 2 1 TraceMate 277V Controls and Indicators Figure 2 2 Typical Wiring Diagram ...

Страница 7: ... Temperature C 6 30 50 8 30 40 10 24 50 12 16 50 The supply voltage must be 277VAC for TM 1SIH1 E5 RTD 277V Single pole TM 1DIH2 E5 RTD 277V Dual pole and rated voltage range of the heat trace cable Wiring methods must conform to Class 1 Division II or Class 1 Zone II requirements Heater Wiring Connect heating cable wiring to terminals 3 and 4 See Figure 2 2 If the heating cable has a braid it sho...

Страница 8: ...m Wiring TraceMate 277V has a form c dry alarm and an active alarm output for driving an LED alarm indicator The alarm LED output is configured to turn on the alarm indicator when there is no alarm Refer to Figure 2 2 for alarm output terminals The form c dry alarm contact is rated 0 1A 30Vdc The alarm LED output is rated 6Vdc 50mA It can drive a 6Vdc LED indicator These alarm contact and output a...

Страница 9: ...ent of a problem Alarm Annunciator If an alarm annunciator or programmable controller is available terminal 10 11 12 can be used as a low cost digital interface These terminals are form c dry con tacts A separate voltage source must be connected across these terminals as shown in Figure 3 2 for the annuncia tor to sense the alarm logic Switching Requirements Two different TraceMate 277V models are...

Страница 10: ...e shut off after a ground fault it is very important that the alarm outputs be used so corrective action can be taken quicklyenough to prevent a process shutdown due to the loss of heat to a pipe Ground fault detection only works with resistance or solidly grounded systems If the system is ungrounded it must be grounded or an artificial ground must be created by means of a zip zag transformer Once...

Страница 11: ...ber generated by S1 9 is interpreted as the high temperature alarm setpoint in C or F The factory default value is 100 C Ground Fault Trip Alarm Setpoint If the jumper on JP1 is at GF position the Setpoint Number generated by S1 9 is interpreted as the ground fault trip alarm setpoint in mA The factory default value is 30 mA Current Fail Alarm Setpoint If the jumper on JP1 is at AMP position the S...

Страница 12: ...can be verified by adjusting the heater setpoint dip switch 2 C above and below a known temperature on the RTD input to see if the heater turns on and off For example if the RTD input temperature is 25 C setting the heater setpoint to 27 C will force the heater on and conversely a 23 C setpoint will force the heater off By substituting a known resistor value for the RTD sensor and looking up the e...

Страница 13: ...round fault sensor as a ground fault Size the resistor according to the table to ensure sufficient ground fault current of 30mA 25 Heater Voltage 110 240 277 AC Volts Resistance 2700 6200 6800 Ohms Wattage 5 10 15 Watts Voltage Rating 250 500 500 DC Volts 4 Apply power The ground fault indicator should come on after a short delay It should not be possible to turn on the heater even if the actual t...

Страница 14: ...OVIDED FOR IN WRITING IN THIS WAR RANTY EACH CONTROL IS PROVIDED WITHOUT ANY WARRANTY OF ANY KIND EITHER EXPRESSED OR IMPLIED IN PARTICULAR WITH OUT LIMITING THE GENERALITY OF THE FOREGOING THE FOLLOW ING IMPLIED WARRANTIES AND CONDITIONS ARE EXPRESSLY DIS CLAIMED a ANY IMPLIED WARRANTY OR CONDITION THAT THE CON TROL WILL MEET YOUR REQUIREMENTS b ANY IMPLIED WARRANTY OR CONDITION THAT THE OP ERATI...

Страница 15: ...TRACEMATE 277V ELECTRONIC THERMOSTAT P N 1501 0013_1 TMII 277V 02 09 Printed in Canada Nextron Corporation 6120 11th Street S E Calgary Alberta T2H 2L7 Tel 403 735 9555 Fax 403 735 9559 ...

Отзывы: