INSTALLATION OF THE CAP
CONNECTOR EARTHING
AND CABLE CLAMPING
NOTE :
A connector/bushing mated combination should not be allowed to carry the full weight of the cable.
Therefore it is necessary to clamp the cable as close as possible to the connector.
IMPORTANT NOTES :
- Never disconnect the connector from energised equipment nor energise a disconnected connector
without previously installing on its appropriate corresponding mating part.
- Do not allow hydrocarbon oils or solvents to contaminate the E.P.D.M. rubber.
In the event of contamination, wipe the surface clean with a dry cloth.
a Nexans company
Nexans Network Solutions NV - div. EUROMOLD
Zuid III - Industrielaan 12
B-9320 EREMBODEGEM-AALST – BELGIUM
Tel: +32 (0)53/85 02 11 – Telefax: +32 (0)53/83 10 13
protective
cap
nylon vent
rod
Installation on insulating plug :
- Clean the inside of the cap and the outside surface of
the connector and insulating plug.
- Place the nylon vent rod along the insulating plug
(see fig.) to exhaust the air during assembly of the cap.
- Push the cap over the connector and on to the
insulating plug.
- Press the centre of the cap on to the locking point
until it snaps in place. Press the cap on all sides to
make sure it is well positioned over the connector.
Position the cap with the pulling tab pointing
downwards.
- Remove the nylon vent rod.
system
earth
cable
clamp
screen
wires
1
Bend back the screen wires along the outer
sheath to form a pig tail.
2
Connect the earthing lead and screen wires to
the system earth.
earthing
lead