equipment
bushing
1
For aluminium conductors : before installing the conductor contact, wire brush the conductor.
2
Fit the contact on to the conductor.
3
Position the crimp contact taking care that the contact hole aligns with the bushing hole.
4
Prior to crimping distance
« Z »
must be between
145
and
160
mm.
5
Crimp the contact. Please refer to the crimp chart for crimp sequence.
6
After crimping distance
« Z »
must be between
145
and
165
mm.
If necessary, adjust the position of the cable reducer until distance
« Z »
is within the tolerance range.
7
Remove any burrs left after crimping and wipe-off excess inhibitor.
CRIMPING/TIGHTENING OF THE CONTACT
Compression type contacts (Type TBC-X)
A
Z
conductor
contact
deep indent
crimping
DIN crimping
contact
palm
Please refer to the crimp chart supplied with the contact.
IS97179-ENG - K480TB/G
-CW45-
CA0 - Revision 3
Page 6 of 10
For
information
only