CONNECTOR EARTHING
AND CABLE CLAMPING
system
earth
cable
clamp
screen
wires
1
Bend back the screen wires along the outer
sheath to form a pig tail.
2
Connect the earthing lead and screen wires to
the system earth.
NOTE :
A connector/bushing mated combination
should not be allowed to carry the full
weight of the cable.
Therefore clamp the cable as close as
possible to the connector.
IMPORTANT NOTES :
- Never disconnect the connector from energised equipment nor energise a disconnected connector
without previously installing on its appropriate corresponding mating part.
- Do not allow hydrocarbon oils or solvents to contaminate the E.P.D.M. rubber.
In the event of contamination, wipe the surface clean with a dry cloth.
earthing
lead
Nexans Network Solutions NV - div. EUROMOLD
Zuid III - Industrielaan 12
B-9320 EREMBODEGEM-AALST – BELGIUM
Tel: +32 (0)53/85 02 11 – Telefax: +32 (0)53/83 10 13
INSTALLATION OF THE CAP
protective
cap
locking
point
protective
cap
Installation on insulating plug BIPR without voltage
detection point :
- Clean the inside of the cap and the outside surface of
the connector and insulating plug.
- Place the nylon vent rod along the insulating plug (see fig.)
to exhaust the air during assembly of the cap.
- Push the cap
firmly
over the connector and onto the
insulating plug.
- Press the cap on all sides to make sure it is well positioned
over the connector. Position the cap with the pulling tab
pointing downwards.
- Remove the nylon vent rod.
Installation on insulating plug BIPA with voltage
detection point :
- Clean the inside of the cap and the outside surface of
the connector and insulating plug.
- Place the nylon vent rod along the insulating plug (see fig.)
to exhaust the air during assembly of the cap.
- Push the cap
firmly
over the connector and onto the
insulating plug.
-
Press the centre of the cap onto the locking point
until it snaps into place.
Press the cap on all sides to
make sure it is well positioned over the connector. Position
the cap with the pulling tab pointing downwards.
- Remove the nylon vent rod.
nylon vent rod
nylon vent rod
IS97179-ENG - K480TB/G
-CW45-
CA0 - Revision 3
Page 10 of 10