3
Insert clamping screw into the threaded hole of the bushing
by hand.
4
Use a torque wrench with a 22 mm socket and tighten exerting
50
Nm (5 kgm or 36,9 foot-pounds) of torque.
In order to achieve the correct applied torque ensure that there is no lubricant on the threaded
parts.
5
Clean and lubricate* the insulating plug for the opposite side of the connector.
6
Insert the plug in the connector and tighten assembly: use a torque wrench with a 6-point socket of 22 mm and
tighten exerting
30
Nm (3 kgm or 22,1 foot-pounds) of torque.
In order to achieve the correct applied torque ensure that there is no lubricant on the threaded
parts.
* USE ONLY THE SILICONE LUBRICANT SUPPLIED
22mm
50 Nm
22 mm
socket
1/2" - 12,7 mm
torque wrench
L ≥ 90 mm
extension
clamping
screw
22mm
30 Nm
1/2" - 12,7 mm
torque wrench
6-point
socket
22 mm
lubricate
basic
insulating
plug
Page 9 of 10
IS97179-ENG - K480TB/G
-CW45-
CA0 - Revision 3
For
information
only