D) Case Grounding

The case of the inverter/charger 

must

 be properly grounded to ship’s ground*.

*Per ABYC A-20:  A DC chassis grounding conductor shall be connected from the case of
the battery charger to the engine negative terminal or its bus, and must not be more than
one size under that required for the DC current-carrying conductors.

For example, if the installed battery wiring (see Wire Size Chart in the following section) is 1
AWG, then the minimum size of the grounding cable is 2 AWG. Use stranded copper wire for
case grounding. A screw compression lug located on the right-hand side of the unit is pro-
vided for attaching the ground wire to the case. The lug accommodates wires up to 1/0
AWG. A flat blade screwdriver is required to tighten the lug.

E) Battery Selection and Sizing

The inverter/charger should only be wired to deep cycle lead-acid batteries of flooded, gel or
AGM construction. The battery bank should be a dedicated inverter (or house) bank. It
should not be connected to batteries which are designed primarily for engine or generator
starting. Those batteries are not designed for repeated deep discharges which are common
with inverter operation.

There are quite a number of variables which can influence the proper size of a battery sys-
tem (expressed as amp-hour capacity) which is used in conjunction with an inverter. Some
of these include:

l

 Battery type

l

 Discharge rate

l

 Intermittent or continuous operation

l

 Ambient temperature

l

 Time between recharge cycles

l

 Depth of discharge

No single formula can practically cover all these variables, however, a general calculation
may be used which assumes no extraordinary variable (such as very high or low tempera-
tures in the battery environment) to make an educated estimation of the proper battery size.
The result can then be adjusted up or down to compensate for unusual circumstances.

Use the following procedure to calculate the required amp-hour capacity for your battery
system:

Note: It is assumed that the batteries are a suitable deep-cycle type, that discharge will
not exceed 50%, and that batteries will be fully recharged after each cycle of inverter
use.

1)

 Determine the maximum amount of time in hours that the inverter will run the

loads before an external source of AC becomes available and batteries can be fully
recharged.

Содержание Guided Wave 12-1200IC

Страница 1: ...AND WARNINGS 3 III INSTALLATION 3 A Materials Provided 4 B Location 4 C Mounting 4 D Case Grounding 5 E Battery Selection and Sizing 5 F Battery DC Wiring 6 G Charging Multiple Battery Banks 8 H AC In...

Страница 2: ...in two stage battery charger for rapid and safe replenishment of batteries whenever shore or generator AC power is available All models feature numerous circuit and safety protections such as thermall...

Страница 3: ...eries is dangerous Batteries generate explosive gasses during operation There is a risk of acid exposure There is also a risk of high current discharge from shorting the battery that can cause fire an...

Страница 4: ...cur as this will shorten its life It should not be located where there is a possibility of dust or debris being drawn into the unit through the fan A minimum of 2 clearance around the unit is recommen...

Страница 5: ...nverter or house bank It should not be connected to batteries which are designed primarily for engine or generator starting Those batteries are not designed for repeated deep discharges which are comm...

Страница 6: ...20 Note These divisors allow for standard inefficiency during voltage conversion 4 Finally since it is generally recommended that batteries never be discharged below 50 the result must be multiplied b...

Страница 7: ...depending on inverter charger model and the length of wire required Wire Size Chart Model Length of Wire from Charger to Batteries in feet 10 15 20 Over 20 Minimum Wire Gauge AWG 12 1200IC 4 2 2 Not R...

Страница 8: ...ect against any possible loosening of the DC wires Install a properly sized and located DC fuse as per ABYC recommendations cited above in the positive leg of the battery wiring then attach the wires...

Страница 9: ...e of a built in automatic transfer switch AC is available directly from the unit at all times either from the inverter or shore generator power Note There is a set of AC wires located in the compartme...

Страница 10: ...ed 2 AC Output Hard Wiring CAUTION Integrating the inverter output with existing AC branch circuits must only be at tempted by a qualified marine electrician Options may include isolating breakers on...

Страница 11: ...panel and incorporates a secondary on off switch for the inverter FIGURE 4 Remote Panel Installation The panel face and mounting hole pattern have been designed for an exact fit within a du plex outle...

Страница 12: ...one of the provided cable clamps in the hole 4 Pass the connector and cable of the remote panel through the clamp then tighten it down securely 5 Snap the plug into the in line assembly and replace th...

Страница 13: ...erefore once batteries are fully charged any DC load on the system within charger rat ing will come directly from the charger not the batteries so there is no need to top off batteries if there have b...

Страница 14: ...lug an AC appliance into each of the two receptacles outlets on the front of the inverter and verify proper operation If the appliance does not operate the black GFCI test button may have been inadver...

Страница 15: ...Indications and Causes Three Shutdown Mode L E D s are provided to indicate an abnormal condition which has caused the inverter to cease functioning temporarily The indicators and likely causes are a...

Страница 16: ...rten the life of the unit and should not be allowed to continue if it is noted VI SPECIFICATIONS MODEL 12 1200IC 12 1799IC 24 1300IC Inverter Output VAC 115V 60 Hz 115V 60 Hz 115V 60Hz Watts Surge 330...

Страница 17: ...over when the ve hicle or boat is in motion A loose battery can do serious damage Batteries should be mounted in a battery box to contain any acid spill Batteries give off a certain amount of hydrogen...

Страница 18: ...ndition of your batteries Battery Condition Table Specific Gravity Measured by State of Hydrometer Open Circuit Voltage Discharge 80 F 12 Volt System 24 Volt System 1 265 12 6 or more 25 2 or more Ful...

Страница 19: ...ground cable and connect an ammeter between the negative battery post and ground If you have a reading over 1 amp there is a source of current drain from the batteries which must be located and remove...

Отзывы: