A) Materials Provided

The inverter/charger is provided with an installation kit containing the following:

(2 ea.) Cable clamps
(1 ea.) Warning label for AC distribution panel
(1 ea.) Installation/Operation Manual
(1 ea.) Customer satisfaction/warranty card

If items any are missing, please contact the factory. Upon completion of the installation,
please fill out the warranty card and return it to the factory. (Be sure to include the serial
number of the unit, located on the top of the housing.)

B) Location

The inverter/charger should be located as close to the batteries as possible, ideally no more
than about 4-6 feet. The maximum allowable distance is 20 feet. Do not mount the unit
directly over the batteries as battery fumes may cause excessive corrosion. 

WARNING: The

inverter/charger is not ignition protected so it must not be located in an area containing gaso-
line engines or the like, nor in any other area where ignition protected equipment is required.

The area should be well ventilated and free from moisture, exhaust manifolds and battery
fumes.

Do not locate the unit where water, spray or condensation can occur, as this will shorten its
life. It should not be located where there is a possibility of dust or debris being drawn into
the unit through the fan. A minimum of 2" clearance around the unit is recommended for
proper cooling.

If the inverter/charger is located in an extreme heat area, such as an unventilated engine
room, and maximum operating temperature is exceeded, an automatic thermal protection
circuit will shut the unit completely off. It will automatically return to service when it has
cooled sufficiently, however this thermal cycling will shorten the life of the inverter/charger,
so if this condition occurs repeatedly, it should be relocated. For optimum performance and
longer life the unit should not be located in an area of high temperature.

C) Mounting

The inverter/charger may be mounted on either a horizontal or vertical surface; performance
will be unaffected by its orientation, however, per UL safety recommendations, when
mounted vertically the front panel controls should be facing downward. It may be mounted
on either a metal or non-metal surface. Four 1/4" screws (wood or machine screws, depend-
ing on mounting surface) with washers are required to secure the unit to the mounting
surface.

IMPORTANT

: Although the inverter/charger is constructed of materials and in a manner

which makes it resistive to the corrosive effects of the marine environment the unit is not
waterproof. Do not mount the charger where there is a possibility of water entering the unit.
Evidence of water entry into the charger will void the warranty.

Содержание Guided Wave 12-1200IC

Страница 1: ...AND WARNINGS 3 III INSTALLATION 3 A Materials Provided 4 B Location 4 C Mounting 4 D Case Grounding 5 E Battery Selection and Sizing 5 F Battery DC Wiring 6 G Charging Multiple Battery Banks 8 H AC In...

Страница 2: ...in two stage battery charger for rapid and safe replenishment of batteries whenever shore or generator AC power is available All models feature numerous circuit and safety protections such as thermall...

Страница 3: ...eries is dangerous Batteries generate explosive gasses during operation There is a risk of acid exposure There is also a risk of high current discharge from shorting the battery that can cause fire an...

Страница 4: ...cur as this will shorten its life It should not be located where there is a possibility of dust or debris being drawn into the unit through the fan A minimum of 2 clearance around the unit is recommen...

Страница 5: ...nverter or house bank It should not be connected to batteries which are designed primarily for engine or generator starting Those batteries are not designed for repeated deep discharges which are comm...

Страница 6: ...20 Note These divisors allow for standard inefficiency during voltage conversion 4 Finally since it is generally recommended that batteries never be discharged below 50 the result must be multiplied b...

Страница 7: ...depending on inverter charger model and the length of wire required Wire Size Chart Model Length of Wire from Charger to Batteries in feet 10 15 20 Over 20 Minimum Wire Gauge AWG 12 1200IC 4 2 2 Not R...

Страница 8: ...ect against any possible loosening of the DC wires Install a properly sized and located DC fuse as per ABYC recommendations cited above in the positive leg of the battery wiring then attach the wires...

Страница 9: ...e of a built in automatic transfer switch AC is available directly from the unit at all times either from the inverter or shore generator power Note There is a set of AC wires located in the compartme...

Страница 10: ...ed 2 AC Output Hard Wiring CAUTION Integrating the inverter output with existing AC branch circuits must only be at tempted by a qualified marine electrician Options may include isolating breakers on...

Страница 11: ...panel and incorporates a secondary on off switch for the inverter FIGURE 4 Remote Panel Installation The panel face and mounting hole pattern have been designed for an exact fit within a du plex outle...

Страница 12: ...one of the provided cable clamps in the hole 4 Pass the connector and cable of the remote panel through the clamp then tighten it down securely 5 Snap the plug into the in line assembly and replace th...

Страница 13: ...erefore once batteries are fully charged any DC load on the system within charger rat ing will come directly from the charger not the batteries so there is no need to top off batteries if there have b...

Страница 14: ...lug an AC appliance into each of the two receptacles outlets on the front of the inverter and verify proper operation If the appliance does not operate the black GFCI test button may have been inadver...

Страница 15: ...Indications and Causes Three Shutdown Mode L E D s are provided to indicate an abnormal condition which has caused the inverter to cease functioning temporarily The indicators and likely causes are a...

Страница 16: ...rten the life of the unit and should not be allowed to continue if it is noted VI SPECIFICATIONS MODEL 12 1200IC 12 1799IC 24 1300IC Inverter Output VAC 115V 60 Hz 115V 60 Hz 115V 60Hz Watts Surge 330...

Страница 17: ...over when the ve hicle or boat is in motion A loose battery can do serious damage Batteries should be mounted in a battery box to contain any acid spill Batteries give off a certain amount of hydrogen...

Страница 18: ...ndition of your batteries Battery Condition Table Specific Gravity Measured by State of Hydrometer Open Circuit Voltage Discharge 80 F 12 Volt System 24 Volt System 1 265 12 6 or more 25 2 or more Ful...

Страница 19: ...ground cable and connect an ammeter between the negative battery post and ground If you have a reading over 1 amp there is a source of current drain from the batteries which must be located and remove...

Отзывы: