B) Inverter ON/OFF Switch Functions

It is important understand the functioning of the ON/OFF switch of the inverter, so that
there can be no incorrect assumption about when AC is being applied within the unit, at the
duplex outlets or the AC hard-wire output.

1)

 The ON/OFF switch (either on the front or remote panel) controls 

only

 whether the

internal DC-AC inverter is operating. 

Whenever external AC is applied

 the internal

battery charger is operational and AC is "live" at both the duplex outlets and
the AC hard-wire output, even if the switch is "OFF". Only shutting off the external AC
at its source will prevent AC flow through the inverter. (Note that, when external AC is
applied the "External" L.E.D. remains illuminated, regardless of which position the
ON/OFF switch is in.)

2)

 If a remote panel is connected and:

a)

 the front panel switch is ON, then  the inverter can be controlled with the

remote ON/OFF switch.

b)

 the front panel switch is OFF, then the inverter remains off, regardless of the

position of the switch on the remote panel.

C) Inverter Shutdown Indications and Causes

Three “Shutdown Mode” L.E.D.s are provided to indicate an abnormal condition which has
caused the inverter to cease functioning temporarily. The indicators and likely causes are as
follows:

1) “Low Input Voltage”

 L.E.D.: Batteries may be permanently damaged by extreme

discharge. Therefore, the inverter monitors battery voltage and shuts off when it
reaches a critical low point (10.5 VDC for models 12-1200IC and 12-1799IC; 21.0
VDC for model 24-1300IC). Typically, this occurs when operating the inverter for long
periods without any external AC source coming on line to recharge the batteries. If
this condition occurs soon after the inverter is turned on, it may be due to an under-
sized, old/weak battery system or to under-sized/over-length battery wiring. Verify
proper battery capacity and health, verify proper wire size and length (see Battery
Wiring section), then recharge fully.

2) “Overload”

 L.E.D.: This may be due to either of two causes; short circuit or too

much wattage demand. Remove all AC loads. If the indicator remains lit, then a short
circuit is likely. Check AC output wiring carefully. If load removal causes this L.E.D.
to be extinguished then the demand is probably exceeding the inverter's rating. Check
the total wattage of all appliances being used at one time and this is within the unit’s
rating.

3) “High Temperature”

 L.E.D.: The inverter employs an integral cooling fan which

operates automatically to keep the unit within rated operating temperature—under

Содержание Guided Wave 12-1200IC

Страница 1: ...AND WARNINGS 3 III INSTALLATION 3 A Materials Provided 4 B Location 4 C Mounting 4 D Case Grounding 5 E Battery Selection and Sizing 5 F Battery DC Wiring 6 G Charging Multiple Battery Banks 8 H AC In...

Страница 2: ...in two stage battery charger for rapid and safe replenishment of batteries whenever shore or generator AC power is available All models feature numerous circuit and safety protections such as thermall...

Страница 3: ...eries is dangerous Batteries generate explosive gasses during operation There is a risk of acid exposure There is also a risk of high current discharge from shorting the battery that can cause fire an...

Страница 4: ...cur as this will shorten its life It should not be located where there is a possibility of dust or debris being drawn into the unit through the fan A minimum of 2 clearance around the unit is recommen...

Страница 5: ...nverter or house bank It should not be connected to batteries which are designed primarily for engine or generator starting Those batteries are not designed for repeated deep discharges which are comm...

Страница 6: ...20 Note These divisors allow for standard inefficiency during voltage conversion 4 Finally since it is generally recommended that batteries never be discharged below 50 the result must be multiplied b...

Страница 7: ...depending on inverter charger model and the length of wire required Wire Size Chart Model Length of Wire from Charger to Batteries in feet 10 15 20 Over 20 Minimum Wire Gauge AWG 12 1200IC 4 2 2 Not R...

Страница 8: ...ect against any possible loosening of the DC wires Install a properly sized and located DC fuse as per ABYC recommendations cited above in the positive leg of the battery wiring then attach the wires...

Страница 9: ...e of a built in automatic transfer switch AC is available directly from the unit at all times either from the inverter or shore generator power Note There is a set of AC wires located in the compartme...

Страница 10: ...ed 2 AC Output Hard Wiring CAUTION Integrating the inverter output with existing AC branch circuits must only be at tempted by a qualified marine electrician Options may include isolating breakers on...

Страница 11: ...panel and incorporates a secondary on off switch for the inverter FIGURE 4 Remote Panel Installation The panel face and mounting hole pattern have been designed for an exact fit within a du plex outle...

Страница 12: ...one of the provided cable clamps in the hole 4 Pass the connector and cable of the remote panel through the clamp then tighten it down securely 5 Snap the plug into the in line assembly and replace th...

Страница 13: ...erefore once batteries are fully charged any DC load on the system within charger rat ing will come directly from the charger not the batteries so there is no need to top off batteries if there have b...

Страница 14: ...lug an AC appliance into each of the two receptacles outlets on the front of the inverter and verify proper operation If the appliance does not operate the black GFCI test button may have been inadver...

Страница 15: ...Indications and Causes Three Shutdown Mode L E D s are provided to indicate an abnormal condition which has caused the inverter to cease functioning temporarily The indicators and likely causes are a...

Страница 16: ...rten the life of the unit and should not be allowed to continue if it is noted VI SPECIFICATIONS MODEL 12 1200IC 12 1799IC 24 1300IC Inverter Output VAC 115V 60 Hz 115V 60 Hz 115V 60Hz Watts Surge 330...