2. Precautions
Read this manual completely and be sure you understand the information provided herein
before attempting to use the product.
Abide by all applicable laws and regulations when using this product.
WARNING
Be sure to ground the product to prevent electric shocks.
If there is a gas leak alarm, take the necessary measures in accordance with your
company's regulations.
The cable entry device and blanking elements shall be of ATEX certified in type of
explosion protection flameproof enclosure ‘’d’’, suitable for the condition of use and
correctly installed.
Unused apertures shall be closed with suitable ATEX certified blanking elements.
Fastener type M5 x 16 shall have a yield stress factor of min. 450 N/mm2.
CAUTION
All necessary work for the product including wiring and installation should be carried out
by suitably trained personnel in accordance with applicable code of practice.
Inspection, maintenance and repair of the equipment should be carried out by suitably
trained personnel in accordance with applicable code of practice.
Do not disassemble the product or modify the construction or electric circuits of the
product. Otherwise, the explosion-proof construction of the product may be adversely
affected.
Do not install the product in places or near places where silicone sealant or gas is used.
Otherwise, the performance of the product may be adversely affected.
Be sure to provide a protective cover (optional) if the product is installed outdoors.
Use the product in accordance with applicable laws and regulations.
Hydrocarbon gas except the target gas might be detected, so consider the measurement
environment.
Special Condition for Safe Use
Use in ATEX hazardous area, ATEX certified cable glands according to EN 60079-0:2012
and EN 60079-1:2007 shall be provided by end-user.
Use in IECEx hazardous area, IECEx certified cable glands according to IEC
60079-0:2011 and IEC60079-1:2007 shall be provided by end-user.
Fastener type M5 x 16 shall have a yield stress factor of min. 450 N/mm2.
Requirement of cable entry:
Thread size of cable entry ………………….G3/4 or PF3/4
Depth of engagement …………………..…..10.86mm
Threads engagement ……………………….6
The dimensions of flameproof joint between casing and casing cover of KD-12
flameproof housing are exceeding the minimum requirements stated EN/IEC60079-1.
Please contact the manufacturer for inspection, repair and/or adjustments of this
flameproof.