Page 10
GAS PRESSURE CHECK
Check the inlet pressure to the burner to ensure that it is as shown in the table below.
NOTE: The pressure check point is located on right side of valve facing the burner.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shut-
off valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than 1/2 psi (3.5 kPa).
MODEL
EMBER VISION 100 AND 200 SERIES
Gas
Natural
Propane (LP)
Maximum Heat Input
40,000
40,000
Minimum Heat Input
31,000
33,000
Gas Inlet Pressure:
Maximum
10.5 ins. W.C. 13.0 ins. W.C.
Minimum
4.5 ins. W.C. 10.5 ins. W.C.
Manifold Pressure
3.5 ins. W.C. 10.0 ins. W.C.
NOTE:
On initial installation it may be required to bleed out air in the gas lines. Do this by
holding the control knob and turning the knob to the pilot position for about 30 seconds.
The pressure should be checked with the heater burning and the control set on high.
After
measuring the pressure, close pressure tap screw, ensuring there are no leaks. Regulator pressure
check screw located above “OFF/
P
ILOT/ON”
knob at right upper corner of valve.
WARNING
This appliance is equipped for (natural or propane) gas.
Field conversion is not permitted.
EMBER VISION SERIES/24” PINE LOG SET SHOWN
LEFT SIDE
RIGHT SIDE
FRONT
#1
#2
#3
#4
#5
#6
#8
#7
#9
Figure 2.