5
5. Data Report
The device will immediately send a version packet report and a data report with the temperature and voltage.
Data will be reported by default setting before any configuration.
Default setting:
Max Interval = 3600s
Min Interval = 3600s (The voltage is detected every Min Interval by default.)
BatteryVoltageChange: 0x01 (0.1V)
Smoke Trigger:
When the device is powered on, it starts smoke detection. When the smoke status changes, the buzzer alarms, the
red indicator flashes, and the device immediately sends a report. (The fire alarm bit is 1.) When the alarm is over,
it sends a report. (The fire alarm bit is 0.)
High Temperature Alarm:
After the device is successfully connected to the network, the temperature will be sampled once every 1 minute.
When the temperature is higher than 60 degrees Celsius, the buzzer will alarm, the red indicator will flash, and a
report will be sent immediately. (The fire alarm bit is 1.) If the alarm continues, the report will be sent every 1
minute. When the alarm is over, that is, when the temperature is below 60 degrees Celsius, a report is sent. (The
fire alarm bit is 0.)
Note:
(1) The device report interval will be programmed based on the default firmware.
(2) The interval between two reports must be the minimum time.
The reported data is decoded by the Netvox LoRaWAN Application Command document and
http://loraresolver.netvoxcloud.com:8888/page/index
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval