background image

6

Example of ConfigureCmd

FPort

0x07

Bytes

1

1

Var (Fix =9 Bytes)

CmdID

DeviceType

NetvoxPayLoadData

CmdID

– 1 byte

DeviceType

– 1 byte – Device Type of Device

NetvoxPayLoadData

– var bytes (Max=9bytes)

(1)

Command Configuration:

MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v

Downlink

010A003C003C0100000000

003C(H

ex)

= 60(D

ec)

Response

810A000000000000000000

Configuration success

810A010000000000000000

Configuration failure

(2)

Read Configuration:

Downlink

020A000000000000000000

Response

820A003C003C0100000000

Current configuration

Description Device CmdID Device

Type

NetvoxPayLoadData

Config

ReportReq

RA02A

0x01

0x0A

MinTime

(2bytes Unit: s)

MaxTime

(2bytes Unit: s)

BatteryChange

(1byte Unit: 0.1v)

Reserved

(4Bytes, Fixed 0x00)

Config

ReportRsp

0x81

Status

(0x00_success)

Reserved

(8Bytes, Fixed 0x00)

ReadConfig

ReportReq

0x02

Reserved

(9Bytes, Fixed 0x00)

ReadConfig

ReportRsp

0x82

MinTime

(2bytes Unit: s)

MaxTime

(2bytes Unit: s)

BatteryChange

(1byte Unit: 0.1v)

Reserved

(4Bytes, Fixed 0x00)

Содержание RA02A

Страница 1: ...ontains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without...

Страница 2: ...1 Table of Content 1 Introduction 2 2 Appearance 3 3 Main Feature 3 4 Set up Instruction 4 5 Data Report 5 6 Installation 9 7 Important Maintenance Instruction 10...

Страница 3: ...ds LoRa spread spectrum modulation technique greatly extend the communication distance It can be widely used in any use case that requires long distance and low data wireless communications For exampl...

Страница 4: ...d alerts can be set via SMS text and email optional Applicable to the third party platforms Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Note Battery life is de...

Страница 5: ...search the network The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network Turn on the device to search the previous network The green indicator...

Страница 6: ...hen the temperature is higher than 60 degrees Celsius the buzzer will alarm the red indicator will flash and a report will be sent immediately The fire alarm bit is 1 If the alarm continues the report...

Страница 7: ...00000000 Configuration failure 2 Read Configuration Downlink 020A000000000000000000 Response 820A003C003C0100000000 Current configuration Description Device CmdID Device Type NetvoxPayLoadData Config...

Страница 8: ...M 1H 25th M 1H 40th M 1H 55th M 2H 10th M Wakes up and collects data 2 8V Does not report Wakes up and collects data REPORTS 2 8V Wakes up and collects data REPORT 2 8V Wakes up and collects data REPO...

Страница 9: ...rts according to MinTime interval If the data variation is not greater than the last data reported the device reports according to MaxTime interval 3 We do not recommend to set the MinTime Interval va...

Страница 10: ...e will send an alarm message When the smoke concentration is lower than the set value and the regular reporting time is up the device will return to the normal state and send the normal message 3 RA02...

Страница 11: ...elt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not thro...

Отзывы: