8
SetDailyReplenishwater
AlarmcountRsp
0x86
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
GetDailyReplenishwater
AlarmcountReq
0x07
Reserved
(9Bytes,Fixed 0x00)
GetDailyReplenishwater
AlarmcountRsp
0x87
DailyReplenishwater
Alarmcount (2Byte)
Reserved
(7Bytes,Fixed 0x00)
(1)
Set fault check time is 180s
Downlink:
03D400B400000000000000 // B4(Hex)=180(Dec)
Device return
:
83D4000000000000000000 (configuration success)
83D4010000000000000000 (configuration failure)
(2)
Clear replenish water count
Downlink:
05D4000000000000000000
Device return
:
85D4000000000000000000 (configuration success)
85D4010000000000000000 (configuration failure)
5.3 Example for MinTime/MaxTime logic
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
Example#2
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
MaxTime
Sleeping(MinTime) sleeping
sleeping
sleeping
0H
15
th
M 30
th
M 45
th
M
1H
2H
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
3.6V
Does not report
Wakes up and
collects data
REPORTS 3.6V
Wakes up and
collects data
REPORT 3.6V
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V