background image

 

 

Data report configuration and sending period are as following: 

 

 

FPort

0x07 

 

Bytes 

Var

 

(Fix =9 Bytes) 

 

CmdID  DeviceType 

NetvoxPayLoadData 

 

CmdID

– 1 byte 

DeviceType

– 1 byte – Device Type of Device 

NetvoxPayLoadData

– var bytes (Max=9bytes)

 

 

1

Configure R313W device parameters: 

MinTime = 1min

MaxTime = 1min

BatteryChange = 0.1v 

 

     Downlink

  0106003C003C0100000000       003C(H

ex) 

= 60(D

ec) 

   

     Device returns

 

                 8106000000000000000000

Configuration success

 

                8106010000000000000000

Configuration failed

 

Min Interval 

(Unit:second) 

Max Interval 

(Unit:second) 

Reportable Change 

Current Change

≥ 

Reportable Change 

Current Change

Reportable Change 

Any number between 

1~65535 

Any number between 

1~65535 

Can not be 0. 

Report 

per Min Interval 

Report 

per Max Interval 

Description 

Device 

Cmd 

ID 

Device 

Type 

NetvoxPayLoadData 

Config 

ReportReq 

R313W 

0x01 

0x06 

MinTime 

(2bytes Unit:s) 

MaxTime 

(2bytes Unit:s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes,Fixed 

0x00) 

Config 

ReportRsp 

0x81 

Status 

(0x00_success) 

Reserved 

(8Bytes,Fixed 0x00) 

ReadConfig 

ReportReq 

0x02 

Reserved 

(9Bytes,Fixed 0x00) 

ReadConfig 

ReportRsp 

0x82 

MinTime 

(2bytes Unit:s) 

MaxTime 

(2bytes Unit:s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes,Fixed 

0x00) 

Содержание R313W

Страница 1: ...td This document contains proprietary technical information which is the property of NETVOX Technology and is issued in strict confidential and shall not be disclosed to others parties in whole or in parts without written permission of NETVOX Technology The specifications are subjected to change without prior notice ...

Страница 2: ...1 Table of Content 1 Introduction 2 2 Appearance 2 3 Main Features 3 4 Set up Instruction 3 5 Data Report 4 6 Installation 8 7 Important Maintenance Instruction 9 ...

Страница 3: ...ommunication methods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring Main features include small size low power consumption transmission distance anti interference ability and so...

Страница 4: ...ry cover Turn on Press any function key till green and red indicator flashes once Turn off Restore to factory setting Press and hold both function keys for 5 seconds till green indicator flashes for 20 times Power off Remove Batteries Note 1 Remove and insert the battery the device memorizes previous on off state by default 2 On off interval is suggested to be about 10 seconds to avoid the interfe...

Страница 5: ...work Sleeping period Min Interval When the reportchange exceeds setting value or the state changes send a data report according to Min Interval Low Voltage Warning Low Voltage 2 4V 5 Data Report When the device is turned on it will immediately send a version package The transmission frequency of sending version package is once every 24 hours Data will be reported once per hour by default setting D...

Страница 6: ... Unit second Max Interval Unit second Reportable Change Current Change Reportable Change Current Change Reportable Change Any number between 1 65535 Any number between 1 65535 Can not be 0 Report per Min Interval Report per Max Interval Description Device Cmd ID Device Type NetvoxPayLoadData Config ReportReq R313W 0x01 0x06 MinTime 2bytes Unit s MaxTime 2bytes Unit s BatteryChange 1byte Unit 0 1v ...

Страница 7: ...ion regardless BatteryVoltageChange value Example 2 based on MinTime 15 Minutes MaxTime 1 Hour Reportable Change i e BatteryVoltageChange 0 1V MaxTime Sleeping MinTime sleeping sleeping sleeping 0H 15th M 30th M 45th M 1H 2H Wakes up and collects data 2 8V Does not report Wakes up and collects data REPORTS 2 8V Wakes up and collects data REPORT 2 8V Wake up and collects data REPORTS 2 8V Wakes up ...

Страница 8: ...e interval 3 We do not recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter resulting from data variation button pushed or MaxTime interval another cycle of MinTime MaxTime calculation is started Wakes up and collects data REPORTS 2 8V Wakes up and co...

Страница 9: ...attach it to a flat ground position where it may accumulate water leaks As shown in the enlarged view on the right The figure shows that the water immersion sensor R313W is used in bathing rooms where there is a possibility of water leakage in the pipeline It can also be applied to the following scenarios Data center and computer room Document storage center Basement leak monitoring Water pipe lea...

Страница 10: ...ion High temperature can shorten the life of electronic devices destroy batteries and deform or melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicat...

Отзывы: