Net Safety Monitoring
MAN-0015 Rev 14 UVIRS-A/AR
12
November 07, 2008
Figure 5: Junction Box Connection
—
A
NALOG
/R
ELAY
B
OARD
WARNING:
If the 4-20mA signal is not used, connect a jumper between the terminals for 4-20mA signal output (SIG) and –PWR(Com-) on the Field Wiring
terminal block.
FIELD WIRING
Terminal Function
RRst Remote
Reset
MVI Manual
VI
SIG
4-20mA Signal Output
-PWR Com
(-)
+PWR Vdc
(+)
FLAME DETECTOR WIRING
Terminal
Wire Function
B
Blue
Manual VI / Communication
R
Red
4-20mA Signal Output
BLK Black
Com
(-)
W White Vdc
(+)
Green
Earth Ground (GND)
Note:
Terminate shield of field wiring at one
end only to Earth Ground.
W
-PWR
+PWR
SIG
MVI
RRst
R
BLK
B
FIRE RELAY
NO
NC
CO
M
CO
M
NC
NO
FAULT RELAY
ON
OFF
1
2
Dip Switch (See “Relay
Settings” for details).
Note:
Connect Green Wire ( Earth GND) to
ground lug of housing.
Relay Contacts
NO Normally
Open
NC Normally
Closed
COM Common