3-2
TRICON/E/E2/E3 Transmitter Installation and Maintenance Guide
Parameter
Description
Minimum
Typical
Maximum
Units
Vcc
Power Supply Voltage
22.5
—
26.5
V
I
S
Power Supply Current
20
—
80
mA
R
L
Loop Resistance
0
—
600
Ω
Gain
Scaling Accuracy
—
—
0.5
%FS
Zero
Offset Accuracy
—
—
0.2
%FS
Vol
Low Digital Pulse Output Voltage
—
0.4
—
V
Voh
High Digital Pulse Output Voltage
8.5
—
12
V
I
ol
Current @ Vol
—
-10
—
mA
I
oh
Current @ Voh
—
10
—
mA
*t
r
l-h
1
Output Rise Time
—
—
2
uS
*t
f
h-l
Output Fall Time
—
—
2
uS
1
Measured with R
L
=2.4K
Ω
and C
L
=50pF
Table 3.2 4-20mA Model (over 0-50°C operating temp)
Parameter
Description
Minimum
Typical
Maximum
Units
Vcc
Power Supply Voltage
11.5
—
26.5
V
I
S
Power Supply Current
20
—
50
mA
Vol
Low Digital Pulse Output Voltage
0
—
—
V
Voh
High Digital Pulse Output Voltage
—
24
26.5
V
I
ol
Current @ Vol
-1.0
—
—
A
I
oh
Current @ Voh
—
0.04
+1.0 W/Voh
A
t
r
l-h
1
Output Rise Time
—
—
2
uS
t
f
h-l
Output Fall Time
—
—
2
uS
1
Measured with R
L
=2.4K
Ω
and C
L
=50pF.
Table 3.3 HF and UP/DN Models (over 0-70°C operating temp)
Содержание TRICON E
Страница 2: ......
Страница 6: ...iv TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...
Страница 8: ...vi TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...
Страница 10: ...viii TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...
Страница 26: ...4 2 TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...
Страница 29: ......
Страница 30: ......
Страница 31: ......