TRICON/E/E2/E3 Transmitter Installation and Maintenance Guide

2-5

Testing the Wires

After wiring the transmitter, double-check to ensure it is wired correctly. Apply
power to the TRICON transmitter and check the output signals as follows:

At No Flow—there should be no pulses out of the digital output terminal,
and a 4mA direct current should be present in the 4-20mA loop.

At 1/2 Flow—the pulse rate out of the digital output terminal should be
1/2 the maximum pulse rate, and a 12mA direct current should be present
in the 4-20mA loop.

At Maximum Flow—the pulse rate out of the digital output terminal
should be equal to the maximum pulse rate, and a 20mA direct current
should be present in the 4-20mA loop.

Final Assembly

Once testing is complete, the transmitter is ready for the final steps of the
assembly process.

1.

Shut off all power to the TRICON.

2.

Place a generous amount of Dow Corning #4 on all exposed wire and
terminals.

3.

Fill the inside of the terminal cover with the moisture compound.

4

Slide the terminal cover in place over the terminal screws.

5.

Fasten the terminal cover with the cover screw and tighten until snug.

Take care not to overtighten the cover screw when securing the terminal cover.

6.

Snap the strain relief fitting over the cable and push it into place in the
cable entry hole.

7.

Wipe away any excess compound.

Mounting the Transmitter

Once the transmitter has been assembled, it is ready to be mounted. If you are
installing a TRICON transmitter on a meter that does not already have a
register mounted on it, skip to step 4. If the meter does have a register
mounted, begin at step 1.

1.

Position the small end of the punch on the center of the seal pin at the base
of the register.

2.

Using the hammer, drive the punch through the center of the seal pin. The
head of the pin should shear off.

3.

Twist the register approximately 1/4 turn counter-clockwise and remove it
from the meter.

Содержание TRICON E

Страница 1: ...TRICON E E2 E3 Transmitter Installation and Maintenance Guide N e p t u n e Te c h n o l o g y G r o u p I n c...

Страница 2: ......

Страница 3: ...TRICON E E2 E3 Transmitter Installation and Maintenance Guide N e p t u n e Te c h n o l o g y G r o u p I n c...

Страница 4: ...ange the product specifications at any time without incurring any obligations Trademarks Used in this Manual Neptune TRICON and Smartrol are registered trademarks of Neptune Technology Group Inc Other...

Страница 5: ...the Transmitter Tools and Materials 2 1 Preparation 2 1 Inspection and Storage 2 1 Safety and Preliminary Checks 2 1 Installation 2 2 Wiring the Transmitter 2 2 Testing the Wires 2 4 Final Assembly 2...

Страница 6: ...iv TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...

Страница 7: ...Figures Figure Title Page 2 1 Elements of the Transmitter 2 2 2 2 Inserting Multi Conductor Cable 2 3 2 3 Creating a Hook in the Wire 2 3 2 4 Connecting the Conductors to the Terminal Screws 2 3 2 5 T...

Страница 8: ...vi TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...

Страница 9: ...2 4 20mA Model over 0 50 C operating temp 3 2 3 3 HF and UP DN Models over 0 70 C operating temp 3 2 3 4 All Models Absolute Limits 3 3 3 5 T 10 Disc Meters 3 3 3 6 T 8 Disc Meters 3 3 3 7 Trident Tur...

Страница 10: ...viii TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...

Страница 11: ...inal Digital Pulse model plus two additional terminals High Resolution Output and Count Direction for connection to a high speed bi directional counter It requires 12 24VDC operating power and is inte...

Страница 12: ...d type of meter with which they are to be used For this reason special care should be taken to ensure that you have the proper Analog 4 20mA model TRICON E required for your application Contact Neptun...

Страница 13: ...ion and Storage Remove the assembly parts from the parts bag and inspect them for any damage The transmitter arrives partially assembled with the terminal cover and mounting ring being the only separa...

Страница 14: ...cross at right angles to minimize noise coupling between wiring Use a dedicated power source such as a separate circuit breaker or isolation transformer for all instrumentation equipment to reduce th...

Страница 15: ...oximately 1 2 from the end of each conductor 6 Using the rounded shaft of the screwdriver form a hook in the end of each bare copper wire See Figure 2 3 7 Loosen the terminal screws as shown in Figure...

Страница 16: ...odel Digital Pulse Model TRICON E3 prior to 1 96 after 1 96 4 20mA Models 1 No Connection High Resolution Output2 4 20mA Source 1 2 No Connection Count Direction2 4 20mA Return 3 12 24VDC Power In 12...

Страница 17: ...2 Place a generous amount of Dow Corning 4 on all exposed wire and terminals 3 Fill the inside of the terminal cover with the moisture compound 4 Slide the terminal cover in place over the terminal s...

Страница 18: ...g upward 6 Align the notch in the base of the register mounting ring with the terminal cover of the TRICON and snap the ring into place When properly oriented the register mounting ring should sit flu...

Страница 19: ...to 158 F 0 to 70 C Storage Temperature 40 to 185 F 40 to 85 C Operating Humidity 0 to 95 RH non condensing Electrical Specifications TRICON E3 Models Parameter Description Minimum Typical Maximum Unit...

Страница 20: ...oh Current Voh 10 mA tr l h1 Output Rise Time 2 uS tf h l Output Fall Time 2 uS 1 Measured with RL 2 4K and CL 50pF Table 3 2 4 20mA Model over 0 50 C operating temp Parameter Description Minimum Typi...

Страница 21: ...3 4 All Models Absolute Limits1 Meter Size Maximum Maximum Minimum Number of Pulse Output Flow Range in Flow Rate Continuous Flow Rate Pulses per Maximum of 4 20mA gpm Flow Rate gpm gpm Gallon1 Flow R...

Страница 22: ...at 20mA Output that is greater than the Maximum Flow Rate allowed for the meter This means that the T 10 type TRICON E running on a T 8 meter will never actually reach the 20mA output level during no...

Страница 23: ...ompound Meter1 Turbine Element Disc Element Size and Type 3 Tru Flo 3 TT 5 8 T 10 4 Tru Flo 4 TT 3 4 T 8 6 Tru Flo 6 TT 1 T 8 2 HP Tru Flo 2 HPT 5 8 T 10 4 Protectus III 4 TT 1 T 10 6 Protectus III 6...

Страница 24: ...2 0 1200 6 2 500 0 7556 37 78 0 2 888 8 4 000 0 6095 40 63 0 4 959 10 6 500 0 5333 57 78 0 9 209 Table 3 10 4 6 8 and 10 HP Protectus III Turbine Elements Performance Specifications2 1 For the High R...

Страница 25: ...mechanical register indication try the following Verify that the TRICON and register match the meter size and type If not replace the TRICON and or the register with the appropriate type to match the...

Страница 26: ...4 2 TRICON E E2 E3 Transmitter Installation and Maintenance Guide Notes...

Страница 27: ...ditions 3 1 equipment 2 1 H HF Models operating temperature 3 2 specifications 3 2 High Performance Turbine See HPT Meters HPT Meters performance data 3 5 humidity operating 3 1 I Inspecting transmitt...

Страница 28: ...3 technical support 1 2 temperature operating 3 1 storage 3 1 terminal cover 2 2 illustrated 2 2 terminal cover hole illustrated 2 2 terminal screws 2 3 illustrated 2 2 temperature storage 2 1 tools...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...34 283 7299 Neptune Technology Group Inc 7275 West Credit Avenue Mississauga Ontario L5N 5M9 Canada Tel 905 858 4211 Fax 905 858 0428 Neptune Technology Group Inc Via Gustavo Baz No 29 C Col Naucalpan...

Отзывы: