PRESSURE SWITCH INSTRUCTIONS 

 

SQUARE D 
Commercial Pressure Switch 

Class 9013, Model FSG29J99

 

 
 

 

Model FSG29J99 

 
 

CUT-OUT RANGE  

20-60 PSI 

 

ADJUSTABLE RANGE  10-30 PSI 

 

CUT-IN RANGE 

10-45 PSI 

 
 

PRESSURE CONNECTION : ¼” NPT EXTERNAL 

 
T

ECHNICAL 

T

ERMS

 

 

Operating Points (Settings) 

Every pressure switch has two operating points; one on rising pressure and one of falling pressure. The operating point on rising 
pressure is referred to as the TRIP POINT or cut out for pumps and compressors and the operating point on falling pressure is 
referred to as the RESET POINT or cut in for pumps and compressors. These operating points are called the SETTINGS of the 
switch. 

— TRIP POINT (rising pressure) 
— RESET POINT (falling pressure) 

 

Differential 

The differential is the difference in pressure between the trip point (cut-out) and the reset point (cut-in). It can be adjustable or 
nonadjustable (fixed).  
 

Example:  

Cut-in 30 psi 
Cut-out 50 psi 
Differential 20 psi (50-30 psi) 

 

Range 

The range is the pressure limits within which the operating points (settings) can be adjusted. The range of the Class 9013 
pressure switch is referenced to the operating point on rising pressure (trip point). The differential subtracts from the trip point 
setting. During the normal operating cycle, system pressure should never exceed the upper limit of the range when using a 
diaphragm actuated switch. This will greatly reduce the life of the diaphragm. 

 

Maximum Allowable Pressure 

Maximum allowable pressure is the pressure to which a switch can be subjected without causing a change in operating 
characteristics, shift in settings, or damage to the device. Pressure surges may occur in a system during the start up of a 
machine or from valve operation. Surges are not normally detrimental to the life of a switch if the surge is within the maximum 
allowable pressure rating of the switch. Diaphragm actuated switches should not be subjected to more than 10 surges per day. 
More frequent surges will greatly reduce the life of the diaphragm. 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

Содержание G-100-1A

Страница 1: ...NEPTUNE GLYCOL FEED SYSTEM Models G 50 1 G 50 1A G 50 2A G 100 1A G 100 2A Lansdale PA 19446 Tel 215 699 8700 Fax 215 699 0370 REV NO 6 01 08 04 ZL106838 OPERATING INSTRUCTION MANUAL...

Страница 2: ...pm pump float switch and NEMA 4X control panel The control panel features a HAND OFF AUTO selector switch for the pump motor ON indication light for the pump LOW tank level indication light and power...

Страница 3: ...stop the pump The minimum differential pressure between the cut in and cut out set points is 10 psi and the maximum is 30 psi The float switch in the bottom of the tank will stop the pump if the glyc...

Страница 4: ...and the other in a clockwise rotation Looking at the front of the Model G XX 2A the control panel facing you the pump motor on the left should be wired counter clockwise and the pump motor on the rig...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...may be readily inspected in the field usually without removal from the drive or system plumbing Simply remove the cover screws to pull the cover Before attempting an inspection follow safety precauti...

Страница 9: ...positioned for easy cleaning access If start up screens are used be sure they are removed prior to placing the system into regular operation Orient lines so as to prevent formation of air pockets Be s...

Страница 10: ...ions require no adjustment If the pump s bearing areas or seal area runs hot shut the pump down and determine the cause For units equipped with integral pressure relief valve the factory setting is us...

Страница 11: ...inimum friction drag with positive sealing and again should be maintenance free provided the same conditions for mechanical seals are met as well as 6 Avoid scouring of the shaft in the lip seal area...

Страница 12: ...ut out 50 psi Differential 20 psi 50 30 psi Range The range is the pressure limits within which the operating points settings can be adjusted The range of the Class 9013 pressure switch is referenced...

Страница 13: ...st the operating points 1 Place a flat blade screwdriver in a range adjustment nut slot 2 Rotate the nut to the left to increase the operating points or to the right to decrease the operating set poin...

Страница 14: ...Cracking will not occur if the bushing is FIRST tightened into the pipe or tank fitting and THEN the L 30 body is tightened into the bushing Thus 1 Teflon tape thread and tighten plastic bushing into...

Страница 15: ...ation and thread gland nut firmly on to cover Fig 1 Wiring schematic for power applied to load when liquid level is less than set point power to load interrupted when level increases to above set poin...

Отзывы: