PRESSURE SWITCH INSTRUCTIONS continued ….. 
 
SET POINT ADJUSTMENTS 

The pressure switch is set at the factory to the operating point(s) marked on the outside of the switch housing. Before 
readjusting the switch, cyle it to determine actual operating points. 
 

Non-Adjustable Differential 

The range adjustment nut ( Item H, Figure 3 ) or knob ( Item C, Figure 3 ) adjusts both setpoints by the same amount.  
To adjust the operating points : 

1. 

Place a flat blade screwdriver in a range adjustment nut slot. 

2. 

Rotate the nut to the left to increase the operating points or to the right to decrease the operating set points. 

 

Adjustable Differential 

The range adjustment nut or knob determines the decreasing setpoint. The adjusting screw ( Item J, Figure 3 ) determines the 
increasing setpoints. To adjust the operating points : 
 

1. 

Adjust the decreasing setpoint ( see steps 1 and 2 above ). 

2. 

Turn the adjusting screw clockwise ( to raise the increasing setpoint ). This adjustment does not affect the 
decreasing setpoint. 

 

 

 

                                               FIGURE 3 

Содержание G-100-1A

Страница 1: ...NEPTUNE GLYCOL FEED SYSTEM Models G 50 1 G 50 1A G 50 2A G 100 1A G 100 2A Lansdale PA 19446 Tel 215 699 8700 Fax 215 699 0370 REV NO 6 01 08 04 ZL106838 OPERATING INSTRUCTION MANUAL...

Страница 2: ...pm pump float switch and NEMA 4X control panel The control panel features a HAND OFF AUTO selector switch for the pump motor ON indication light for the pump LOW tank level indication light and power...

Страница 3: ...stop the pump The minimum differential pressure between the cut in and cut out set points is 10 psi and the maximum is 30 psi The float switch in the bottom of the tank will stop the pump if the glyc...

Страница 4: ...and the other in a clockwise rotation Looking at the front of the Model G XX 2A the control panel facing you the pump motor on the left should be wired counter clockwise and the pump motor on the rig...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...may be readily inspected in the field usually without removal from the drive or system plumbing Simply remove the cover screws to pull the cover Before attempting an inspection follow safety precauti...

Страница 9: ...positioned for easy cleaning access If start up screens are used be sure they are removed prior to placing the system into regular operation Orient lines so as to prevent formation of air pockets Be s...

Страница 10: ...ions require no adjustment If the pump s bearing areas or seal area runs hot shut the pump down and determine the cause For units equipped with integral pressure relief valve the factory setting is us...

Страница 11: ...inimum friction drag with positive sealing and again should be maintenance free provided the same conditions for mechanical seals are met as well as 6 Avoid scouring of the shaft in the lip seal area...

Страница 12: ...ut out 50 psi Differential 20 psi 50 30 psi Range The range is the pressure limits within which the operating points settings can be adjusted The range of the Class 9013 pressure switch is referenced...

Страница 13: ...st the operating points 1 Place a flat blade screwdriver in a range adjustment nut slot 2 Rotate the nut to the left to increase the operating points or to the right to decrease the operating set poin...

Страница 14: ...Cracking will not occur if the bushing is FIRST tightened into the pipe or tank fitting and THEN the L 30 body is tightened into the bushing Thus 1 Teflon tape thread and tighten plastic bushing into...

Страница 15: ...ation and thread gland nut firmly on to cover Fig 1 Wiring schematic for power applied to load when liquid level is less than set point power to load interrupted when level increases to above set poin...